background image

P:\INSTALLATION INST\Power Supplies\INST-631RF_631RFA.vsd      Rev C      01-12

REGULATED POWER SUPPLY

INSTALLATION INSTRUCTIONS

MODEL 631RF/631RFA

SECURITY DOOR CONTROLS

801 Avenida Acaso, Camarillo, Ca. 93012

(805) 494-0622  •  Fax: (805) 494-8861

www.sdcsecurity.com  •  E-mail: service@sdcsecurity.com

POWER SUPPLY SPECIFICATIONS

Input Voltage: 115/230 VAC @ 60hz
Input Current: 0.8 amps Max.

Output Voltage: 12/24VDC (Special Applications)
Output Current: 1.5 amps
Ripple Voltage: 0.05 Volts Max

Battery Charger Max Current: 0.25 amps
Maximum recommended battery size: 7ah
(Replace batteries every three years)

To determine standby battery capacity, refer to
Batter Discharge table (INST-BDT).

Compatible UL listed Fire Devices:
Smoke detector manufactured by ESL, Model 521B,
521BXT with Model 506 module.

Suitable Uses:
Electric Lock Power Supply
Access Control Power Supply
Burglar Alarm System Power Supply

NOT INTENDED TO POWER A LOCAL
BURGLAR ALARM INDICATING DEVICE.

TEST UNIT YEARLY

COMPONENT LOCATIONS

STANDARD BOX

POWER

SUPPLY

BOARD

CONTROL
MODULE

CONTROL
MODULE

BATTERY 1

4ah

BATTERY 2

4ah

MAIN SYSTEM ON-OFF

OR

FIRE PANEL CONNECTION

Fire Panel

Contact (N/C)

Master ON/OFF

Switch (N/C)

+ _

C

Figure C

C

+ _

Min. Switch

OR

Contact Ratings
100mA @ 30vdc

12VDC

+

_

12VDC

+

_

JUMPER SET

FOR 24 VDC

+

-

JUMPER SET

FOR 12 VDC

12VDC

+

_

+

-

12 Volt mode Battery

Connections

+

C

-

Battery

Charger

Indicator

Fuse

AC Power

LED

Primary
Fuse 250V
1.5Amp

Battery
Input

Voltage Output

Terminals

12V

S
H
O
R
T

O
P
E
N

24V

VOLTAGE 

SELECT

System Status

LED

Voltage

Adjust

Note:
Power must be 
turned off before 
changing voltage 
jumper

See figures b & c for examples of 

Master System On/Off Control

OR

Power Supply control from

the Fire Control Panel

FIGURE A

“A” OPTION BOX

POWER

SUPPLY

BOARD

CONTROL
MODULE

CONTROL
MODULE

BATTERY 2

4ah or 7ah

CONTROL
MODULE

CONTROL
MODULE

BATTERY 2

4ah or 7ah

FIGURE B

24 Volt mode Battery

Connections

NOTE:
Power limited cable 
must maintain a 1/4” 
or more spacing from 
battery cables or 
primary power wires.

_

Battery

+

Power limited
Class 2 output

631RF

High voltage
Input

+ - + -

C

Wire Routing

Reviews: