Configure Sense Input
Default: Door Sense
The Sense Input (gray wire) can be programmed for either
DOOR SENSE or INHIBIT.
Press: 10 # Input #
Input=0 for Door Sense; =1 for Inhibit
When programmed for DOOR SENSE, if an open condition on
the input occurs before access is granted (with an entry code or
with the request-to-enter input) a FORCED ENTRY output will
occur. If an open condition remains 60 seconds after a relay
activation for access, a DOOR AJAR output will occur.
When programmed for INHIBIT, a closed condition on the input
will prevent Relay #1 from activating when access is requested
with an entry code. This mode is typically used with an external
timer to disable the access device at certain times.
Select Forced Entry Output
Default: No Output
Sets which output activates if the DOOR SENSE input opens
before access is granted. This output is timed and configured
by the relay “On-time”.
Press: 11 # Output #
Output=Output to Activate(0-4)
1=Main Relay; 2=Auxiliary Relay; 3=Output #3; 4=Output #4;
0=No Output
Select Door Ajar Output
Default: No Output
Sets which output activates if the DOOR SENSE input stays
open 60 seconds after access is granted (door ajar time is
adjustable using Function 25). This output is not timed.
Press: 12 # Output #
Output=Output to Activate (0-4)
1=Main Relay; 2=Auxiliary Relay; 3=Output #3; 4=Output #4;
0=No Output
Select Keypad Active Output
Default: No Output
Sets which output activates when any keys are pressed. This
output is timed. If toggle mode is selected for the output, the timer
value defaults to 2 seconds.
Press: 14 #
Output
#
Output=Output to Activate(0-4)
1=Main Relay; 2=Auxiliary Relay; 3=Output #3; 4=Output #4;
0=No Output
Select Keypad Lockout Output
Default: No Output
Sets which output activates when the keypad is “locked out” after
too many incorrect entry code attempts. The lockout time is 60
seconds.
Press: 13 #
Output
#
Output=Output to Activate (0-4)
1=Main Relay; 2 = Auxiliary Relay; 3=Output #3; 4=Output #4;
0=No Output
Select Alarm Shunt Output
Default: No Output
Sets which output activates during the time access is granted.
(Use this output ot shunt alarm contacts attached to the access
door.) This output may be timed or toggled.
Press: 15 #
Output
#
Output=Output to Activate(0-4)
1=Main Relay; 2=Auxiliary Relay; 3=Output #3; 4=Output #4;
0=No Output
Select Request-to-Exit Output
Default: No Output
Sets which output activates when the Request-to-Exit input is
grounded. This output may be timed or toggled.
Press: 16 #
Output
#
Output=Output to Activate(0-4)
1=Main Relay; 2=Auxiliary Relay; 3=Output #3; 4=Output #4;
0=No Output
REX input terminates toggle of Main or Aux. Relay
Main Relay On-time
Default: 02 Seconds
Sets the length of time the Main Relay activates when triggered.
Green LED is on when Main Relay is active.
Press: 21 #
Seconds
#
Seconds=Output time in seconds (1-60)
Auxiliary Relay On-time
Default: 02 Seconds
Sets the length of time the Auxiliary Relay activates when triggered.
Press: 22 #
Seconds
#
Seconds=Output time in seconds (1-60)
P:\INSTALLATION INST\Access Controls\INST-920\INST-920.vsd Rev C 10-14 Page 5
Anti-Tamper Output
Default: No Output
Sets which output activates when the Anti Tamper switch on the
back of the keypad is activated.
Press: 17 #
Output
#
Output=Output to Activate(0-4)
0=No Output; 2=Auxiliary Relay; 3=Output #3; 4=Output #4;
Changing the 6-Digit Master Programming Code
Press: 98 #
Master Code
#
Master Code
#
Master Code=The new 6-digit Master Programming Code
Erasing All Entry Codes
WARNING: PERFORMING THIS COMMAND WILL REMOVE
ALL ENTRY CODES FROM THE MEMORY
Press: 97 # 0 0 0 0 0 0 # 0 0 0 0 0 0 #
Note:
The green indicator will light while the memory is being erased. This
may take up to 15 seconds.