Beep Sounds During Auxiliary Relay

Default: No

Selects whether or not the keypad beeps during Auxiliary Relay 
activation.

Press: 4 2 # Sound #  

Sound=1 for Yes, =0 for No

Beep Sounds During Output #3

Default: No

Selects whether or not the keypad beeps during Output #3 
activation.

Press: 4 3 # Sound #  

Sound=1 for Yes, =0 for No

Beep Sounds During Output #4 

Default: No

Selects whether or not the keypad beeps during Output #4 
activation.

Press: 4 4 # Sound #  

Sound=1 for Yes, =0 for No

Keypad Lockout Count

Default: 3 Tries

Sets the number or incorrect entry code attempts allowed 
before the keypad “locks out”.

Press: 5 0 # Attempts #  

Attempts=Number of attempts before lockout (2-7)

Anti-Pass Back Time

Default: No Anti-Pass Back

Sets the length of time an entry code will not function after it is 
used.

Press: 5 1 # Minutes #  

Minutes=Time in minutes (1-4), 0=No Anti-passback

RESETTING KEYPAD

Master Reset

CAUTION:  Performing a master reset will clear the 
entire memory of the 923 and return all programmable 
options to the factory default values.  ALL ENTRY 
CODES WILL BE ERASED. NOTE:  The Master Code will 
NOT be reset.

STEP 1

Disconnect power from the keypad.

STEP 2

Press and hold down the * and # keys.

STEP 3

Apply power to the keypad, continue holding the keys 
down until the red indicator starts flashing

STEP 4

Release the keys.  The red and yellow indicators will 
remain lit until the process is complete, then the 
yellow indicator will go out.

Resetting the Master Code

STEP 1

Remove the 923 from the wall and disconnect 
power from the keypad.

STEP 2 

Locate & Remove jumper at JP2.  Reference page 2.  

STEP 3

Re-apply power.  You will get a single beep and 
the yellow LED will flash momentarily.

STEP 4

Replace jumper on JP2.

THE MASTER PROGRAMMING CODE IS NOW 123456.

Beep Sounds During Main Relay

Default:  No

Selects whether or not the keypad beeps during Main Relay 
activation.

Press: 4 1 # Sound #  

Sound=1 for Yes, =0 for No

Solid-state Output #4 On-time

Default:  02 Seconds

Sets the length of time Output #4 activates when triggered.

Press: 2 4 # Seconds #  

Seconds=Output time in seconds (0-60), 99=Toggle Mode

Beep Sounds on Keystrokes

Default:  Yes

Selects whether or not the keypad beeps as each key is pressed.

Press: 4 0 # Sound #  

Sound=1 for Yes, =0 for No

P:\INSTALLATION INST\Access Controls\INST-923\INST-923.vsd     Rev F     05-19     Page 6

Selects mode for Keypad LED Backlight

Default: 30 Seconds

Selects whether or not the keypad back light stays OFF, lights for 30 
seconds when activated or stays ON.

Press: 52 # Output #  

0 = Light always OFF

1 = 30 sec light when activated (default)

2 = Light always ON 

Door Ajar Timer

Default:  60 Seconds

Sets the amount of time the door may be held open after an 
authorized access.  The DOOR AJAR output will activate after the 
time expires.

Press: 25 # Seconds #  

Seconds=Held open time in seconds (1-60)

Changing the Beeper Sound Level

The Keypad’s beeper can be set to high or low level.
Remove jumper JP1 to reduce beeper sound level.

Solid-state Output #3 On-time

Default:  02 Seconds

Sets the length of time Output #3 activates when triggered.

Press: 2 3 # Seconds #  

Seconds=Output time in seconds (0-60), 99=Toggle Mode

Changing the 6-Digit Master Programming Code

Press: 9 8 # Master Code Master Code #  

Master Code=The new 6-digit Master Programming Code

New master code: ____________

Summary of Contents for EntryCheck 923

Page 1: ...ill prevent tailgating by turning off the Main Relay output immediately when the door is closed after access has been granted If the SENSE input is programmed for inhibit the input can be wired to a service switch or automatic timer that will disable the Main Relay when required The REQUEST TO EXIT input can be wired to a pushbutton to provide codeless activation of Main Relay Auxiliary Relay Outp...

Page 2: ...56 Enter the program mode default master code Step 2 Enter 03 4 Set the entry code length to 4 digits Step 3 Enter 21 5 Set the main relay activation time for 5 sec Step 4 Enter Exit programming mode QuickStart Programming You must first enter programming mode to perform any function The yellow indicator will blink slowly showing that the 923 EntryCheck is in programming mode Use the option codes ...

Page 3: ...es this unit must be connected to a proper earth ground Connect the green earth ground wire to a good earth grounding point Suggested wiring size is 18 AWG for earth ground Sense Input RE Note The SENSE input gray wire can be programmed as either a door sense or inhibit input Both features cannot be used at the same time If you are not using the sense input program this input for inhibit Door Sens...

Page 4: ...ation in memory The green indicator will light when the new user is accepted If the user number already exists or an entry error has been made the red indicator will light Delete the user and re enter the new information again Note Leading zeros zeros before the Code number i e 0001 do not need to be entered when programming a new code The 923 will internally add any zeros to fill digits determine...

Page 5: ... No Output Select Keypad Lockout Output Default No Output Sets which output activates when the keypad is locked out after too many incorrect entry code attempts The lockout time is 60 seconds Press 1 3 Output Output Output to Activate 0 4 1 Main Relay 2 Auxiliary Relay 3 Output 3 4 Output 4 0 No Output Select Alarm Shunt Output Default No Output Sets which output activates during the time access i...

Page 6: ... Locate Remove jumper at JP2 Reference page 2 STEP 3 Re apply power You will get a single beep and the yellow LED will flash momentarily STEP 4 Replace jumper on JP2 THE MASTER PROGRAMMING CODE IS NOW 123456 Beep Sounds During Main Relay Default No Selects whether or not the keypad beeps during Main Relay activation Press 4 1 Sound Sound 1 for Yes 0 for No Solid state Output 4 On time Default 02 S...

Page 7: ...P INSTALLATION INST Access Controls INST 923 INST 923 vsd Rev F 05 19 Page 7 4X Mount at holes With supplied screws and hole expansion anchors 1 375 7 3125 1 750 WALL MOUNT MULLION MOUNT ...

Reviews: