2012.03 / e
LEROY-SOMER
9
Installation and maintenance
R 450
AVRs
4531 en -
WARNING
The limitation threshold must be
adjustable between 1 and 5.5 A. The
genset breaker must be open during the
short circuit. If the genset is restarted in
short circuit, there is a excitation build
up during 10s again at the maximum
value.
Operation between 3 and 6 In when
short-circuited:
The excitation current ceiling during a
short-circuit equals 2.9 times the fixed
threshold when setting the permitted
excitation ceiling in continuous operation.
When the threshold is exceeded for a period
= 10 s the current is reduced to a value
between 0.5 and 0.7 A (shutdown).
In all operating conditions the maximum
excitation current must be limited to
9 A ± 0.5 A.
Overrun indications:
One green LED:
- Lights up when the excitation current is
below the continuous operation threshold
It signals the AVR normal operation.
- Turns off when the excitation current ceiling
used to obtain short-circuit operation is
reached and when the excitation current is
reduced to the shutdown value.
- Flashes when the over excitation counter
is decrementing.
NB: After an obvious short-circuit, the
voltage is limited to 70% of the rated voltage.
This avoids overvoltages on machines
whose no-load excitation current is below
the “lower current” threshold (only in AREP).
P3
Diagram 1
9.5
I exc(A)
(Maximum current I exc)
Decrease of
90 s tempo.
Activation of
90 s tempo.
Activation of
90 s tempo.
Red led
Green led
Activation of
10 s tempo.
10s tempo. elapsed :
shutdown apllication
t(s)
2.9x I
threshold
(max. 9.5 A)
I
threshold
(1...5.5A)
Shutdown
0.5 ~ 0.7
269/297
Summary of Contents for R570U
Page 1: ...User and maintenance manual for generating sets R570U 33504081501NE_1_1 ...
Page 15: ...Alternator Cabinet Figure 1 3 Examples of identification plates 13 297 ...
Page 18: ...Sockets voltage 208 120V 16 297 ...
Page 125: ...9 Appendix 9 1 Appendix A Engine user and maintenance manual 123 297 ...
Page 126: ...124 297 ...
Page 128: ...126 297 ...
Page 129: ...OPERATOR S MANUAL Generating set and industrial engines 16 liter EMS 2 127 297 ...
Page 159: ...157 297 ...
Page 218: ...216 297 ...
Page 220: ...218 297 ...
Page 222: ...7748681 English 12 2011 220 297 ...
Page 223: ...9 2 Appendix B Alternator user and maintenance manual 221 297 ...
Page 224: ...222 297 ...
Page 226: ...224 297 ...
Page 250: ...www leroy somer com 248 297 ...
Page 261: ...Installation and maintenance R250 A V R 4067 en 2009 05 b LEROY SOMER 11 259 297 ...
Page 281: ...2012 03 e LEROY SOMER 19 Installation and maintenance R 450 AVRs 4531 en 279 297 ...
Page 282: ...www leroy somer com 280 297 ...