6.2.4.3.
Activation of an alarm and a fault
The appearance of an alarm
and
a fault causes:
The yellow and red LEDs to flash
the related screen to be displayed (example below)
FAULTS 1/2
FAULT
Emergency Stop
25/12/05 15:30
Esc=RESET OK=LIST
If several faults are present, the number of faults is displayed at
the top of the screen.
The faults list can be accessed by pressing OK (of the scrolling and selection wheel) (examples below)
FAULTS
1/2
FAULT 25/12/05 15:30
Emergency Stop
ALARM 25/12/05 15:30
Low Fuel Level
OK=HELP Esc
Press Esc to return to the previous screen.
Press OK to go to the HELP screen (help on the highlighted
fault)
Use the scrolling and selection wheel to scroll through the list of
faults.
HELP
Check:
- Emerg. Stop Pos.
- Connector(s)
Esc
If the alarm is no longer active, it is reset automatically (cause disappears).
Press Esc to reset a fault:
-
reset acknowledged if the cause of the fault has been removed
-
reset not performed if the cause of the fault is still present.
50/297
Summary of Contents for R570U
Page 1: ...User and maintenance manual for generating sets R570U 33504081501NE_1_1 ...
Page 15: ...Alternator Cabinet Figure 1 3 Examples of identification plates 13 297 ...
Page 18: ...Sockets voltage 208 120V 16 297 ...
Page 125: ...9 Appendix 9 1 Appendix A Engine user and maintenance manual 123 297 ...
Page 126: ...124 297 ...
Page 128: ...126 297 ...
Page 129: ...OPERATOR S MANUAL Generating set and industrial engines 16 liter EMS 2 127 297 ...
Page 159: ...157 297 ...
Page 218: ...216 297 ...
Page 220: ...218 297 ...
Page 222: ...7748681 English 12 2011 220 297 ...
Page 223: ...9 2 Appendix B Alternator user and maintenance manual 221 297 ...
Page 224: ...222 297 ...
Page 226: ...224 297 ...
Page 250: ...www leroy somer com 248 297 ...
Page 261: ...Installation and maintenance R250 A V R 4067 en 2009 05 b LEROY SOMER 11 259 297 ...
Page 281: ...2012 03 e LEROY SOMER 19 Installation and maintenance R 450 AVRs 4531 en 279 297 ...
Page 282: ...www leroy somer com 280 297 ...