Vigilant User Manual
113/232
12.17.1.
Waveform only
Field
Description
Tag
Text that unequivocally identifies the
Processing Mode
within the
Point
. Only ASCII
alphanumeric characters are allowed, including ”.”, “
-
”, and “_”. Any other special
characters or blank spaces are not allowed. First character must be alphanumeric.
Maximum length is 25 characters.
Name
Text used on the
Dashboard
to identify the
Processing Mode
. ASCII alphanumeric
characters are allowed, including ”.” , “
-
” , “_” and blank spaces. If none is given the tag
will be used.
Description
Allows the user to include a description of the
Processing Mode
Type
Shows the type of
Processing Mode
.
Sampling rate
Sets the sampling frequency the
Processing mode
will use. The sampling rate and units
are selected from the correspondent pull-down menus. The options available are 320
Hz, 400 Hz, 640 Hz, 800 Hz, 1280 Hz, 1600 Hz, 2560 Hz, 3200 Hz, 5120 Hz, 6400 Hz, 12800
Hz, 25600 Hz and 51200 Hz.
Samples
Sets the number of samples of the waveform that will be stored on the database and
shown in the interface. The maximum value allowed is 262016 samples.
Duration
Informs about the time duration of the waveform in seconds. This value will depend on
the number of samples and maximum frequency defined for the
Processing Mode
.
Buffer size
Informs about the number of samples that will be stored at the buffer memory in order
to measure the waveform. This value depends on the number of samples defined and
the filters required (anti-aliasing).
Keep data
Keeps or discards the waveform measurement after calculating all the parameters
associated to the
Processing mode
. If this checkbox is not enabled the waveform data
will not be kept and will not be able to be stored.