Vigilant User Manual
95/232
Field
Description
Tag
Text that identifies unequivocally the
Machine
. Only ASCII alphanumeric characters
are allowed, including ”.”, “
-
”, and “_”. Any other special characters or blank spaces
are not allowed. The first character must be alphanumeric. Maximum length is 25
characters.
Enabled
Enables or disables the
Machine
within the unit. Disabling it will cause the unit to
completely ignore the
Machine
. The
Dashboard
will not show it in the interface and
the system will not measure it. The configuration tree will indicate this by displaying
the text
Disable
by the
Machine
name.
Name
Text used on the
Dashboard
to identify the
Machine
.
Description
Text describing the
Machine
.
Manufacturer
Defines the
Machine
manufacturer.
Model
Defines the model of the
Machine
.
Serial Number
Defines the serial number that identifies the
Machine
.
Support class
Defines from a pull-down menu the ISO 10816-3 Support class that will be assigned
to the machine.
Rated power
Defines the rated power of the
Machine
in kW
Image
Assigns an image to the
Machine
. This image will be shown in the
Dashboard
using
the
Mimic Widget
.
Enabled
(monitoring)
Enables/disables the monitoring of the
Machine
. When disabled the
system
will not
measure or store any data. However, existing data will be available in the
Dashboard
. The configuration tree will indicate this by displaying the text
Monitoring
off
by the
Machine
name.
Period
Sets the refreshing rate (monitoring period) for the measurements of the
Machine
in seconds. This is independent on the sampling time required for each
Processing
mode
due to the pre-buffering capabilities of the VIGILANT.
Delay at start-
up
Defines a delay time the system will wait for before starting the monitoring of the
Machine
after a new configuration has been applied. This delay allows
accelerometers to stabilize by waiting for its settling time to elapse.
Buffer size
Indicates the maximum number of samples required to monitor this machine in all
of the points and processing modes defined in its configuration.
Tachometer
Sets the point that will be used to measure the speed of the
Machine
. It may either
be a
Pulse tachometer
point or a
Static
point (Static
Inputs
,
Modbus
,
OPC
or
Formula
)
with speed output format (
Speed
units).
Rated speed
Nominal speed of the
Machine
. It can be defined in CPM or Hz.
Load point
Sets the point that will be used to measure the load of the
Machine
.
Rated load
Nominal load of the
Machine
. It can be defined in any of the magnitudes and units
set up in the system.
Alarms
Provides a quick access to the
Alarm
menu, which allows a quick and easy
configuration of alarm levels for all the parameters.