background image

 

Page 2 of 11

   

123-652 Rev - 

 

1

 

GENERAL SPECIFICATIONS 

 

Operating Voltage: 12 - 32 VDC 
Backup Power Supply: 12 - 32 VDC 
Power Supply Protection: 3A Fuses 
Internal Voltage Protection - 3 diodes  
Pressure Switch - 2 normally closed inputs 
Visual Indications - POWER - Green 
 

 

       PS1 - Red 

 

 

       PS2 - Red 

Buzzer: 85 dB @ 10 cm 
Standby Power Consumption (All three Models) 
 

 

 

13 VDC, 100 mA 

 

 

 

28 VDC, 100 mA 

Discharged Power Consumption 
 

PN: 131-740: 13 VDC, 370 mA 

 

 

        28 VDC, 180 mA 

 

PN: 131-745: 13 VDC, 570 mA 

 

 

        28 VDC, 260 mA 

 

PN: 131-750: 13 VDC, 750 mA 

 

 

        28 VDC, 350 mA 

Enclosure Material: Grey flame retardant ABS 
Flame Rating: UL94-5VA (with textured cover) 
Enclosure Protection level: Ingress protection 66 (IP66) 
Operating Temperature: -7

o

C/20

o

F to 54

o

C/130

o

Storage Temperature: -7

o

C/20

o

F to 54

o

C/130

o

Display Connection: CAT-5 VIA RJ45 Socket 
Relays: 5 VDC Form C – Normally Open (N/O) 20A 

            Normally Closed (N/C) 10A 

Connectors - Wago 739, Max wire size 12AWG/2.5 mm 
Dimensions: 7.29 (W) x 4.72(H) x 2.37(D) inch 
 

        185.17(W) x 119.89(H) x 60.20(D) mm 

Weight: .6 kg / 1.3 lb. 
Mounting: Surface 
Compliant: RoHS, CE 

       
 
 
 

 
 
1.1

 

Features 

 

Fully automatic machinery shutdown system 

 

Shutdown override mode  

 

Power-On visual indication 

 

Pressure Switch (PS1) Visual and audible indication (Agent Discharge) 

 

Pressure Switch (PS2) Visual and audible indication (Sensor Switch Warning) 

 

Compact construction 

 

Optional Time Delay reset function  

 
 
2

 

OPERATION 

 
The Machinery Shutdown Restart unit is a low voltage microcontroller unit designed to integrate with the Sea-Fire Fire 
Suppression System to shut down the engine(s), blower(s), generator(s), damper(s) and other machinery in the protected 
space should fire or extreme overheating cause the Sea-Fire automatic Fire suppression system to discharge.  The 
machinery shutdown will ensure that the fire suppression agent, in its proper concentration, will remain in the enclosed 
compartment and not be ingested or reduced by the running machinery.   
 
Immediately upon agent discharge, the MSRS PS1 closed loop circuit opens, activating the alarm and energizing all the 
relays.  Energizing the relays will change the state of the internal contacts and shut down all the machinery connected to 
the MSRS unit.  The PS1 LED on the Unit and the DISCHARGE LED on the Display Panel illuminate.  The activated alarm can 
be silenced by pressing the SILENCE button on the MSRS unit or on the connected Display Panel.   
After a discharge or loss in cylinder pressure resulting in an opened PS1 loop, simultaneously pressing the SILENCE and the 

” buttons will put the MSRS into override enabling all the machinery connected to the MSRS to restart.  The MSRS can 

only be properly reset after the discharged agent cylinder has been refilled/replaced and then the SHUTDOWN RESET 
buttons pressed to put the unit back into the standby mode.  In the standby mode, only the green POWER LED on the MSRS 
and the Display Panel will remain on.   
 

Summary of Contents for 131-740

Page 1: ... Sea Fire automatic and manual Fire Suppression Systems Installation must be accomplished by or under the supervision of a qualified marine electrician who is familiar with American Boat and Yacht Council ABYC or other recognized and accepted marine standards and practices Caution Do not install this device in fuel storage compartments See the installation section of this manual for further detail...

Page 2: ...reset function 2 OPERATION The Machinery Shutdown Restart unit is a low voltage microcontroller unit designed to integrate with the Sea Fire Fire Suppression System to shut down the engine s blower s generator s damper s and other machinery in the protected space should fire or extreme overheating cause the Sea Fire automatic Fire suppression system to discharge The machinery shutdown will ensure ...

Page 3: ...led in a box or cabinet the enclosure should have sufficient ventilation When installed in the engine room the MSRS should be installed with sufficient protection from the hazards of that space but must still have a way to dissipate heat and not be overheated by other sources WARNING Do not install the MSRS Unit in a sealed enclosure 3 2 Mounting the MSRS Unit Use the MSRS unit 4 mounting screw ho...

Page 4: ...l open activating the early warning alarm o Temperature Sensor When the temperature in the protected zone goes above the fixed temperature of the sensor the sensor shall open activating the early warning alarm 3 3 1 3 Power Supply Terminals Main Supply Backup Supply and Generator The MSRS Unit has 3 diode protected inputs but only one power source is needed to operate the MSRS and should be connec...

Page 5: ...l the cylinder supervisory switches in series Connect the leading switch wire to Terminal marked 3 and the trailing wire of the last pressure switch to Terminal marked 4 See Figure 2 When connecting more than one Engineered System discharge pressure switch reference the engineered fire suppression manual and electrical circuit diagram provided as part of the system 3 3 1 6 Engine or Machinery conn...

Page 6: ...down the alarm should sound and the red PS1 LED on the MSRS Unit should illuminate as well as the red Discharge LED on the Display Panel 6 Press the SILENCE button on the Display Panel or on the MSRS Unit to silence the alarm 7 With the PS1 circuit still open put the MSRS into override by simultaneously pressing the SILENCE and the buttons on display panel a The connected machinery should be able ...

Page 7: ... is not making good contact with the terminals Recycle power to the MSRS unit Remove and re install jumper The MSRS has an internal fault Recycle power to the MSRS unit Replace the MSRS unit 4 The PS1 and the PS2 LED are on the Alarm does not silence AND the unit does not reset The MSRS has an internal fault Replace the MSRS unit 5 The SILENCE button on the MSRS unit does not silence the alarm The...

Page 8: ...C MAY APPLY PER CUSTOM CONFIGURATION DIAGRAMS NOTE THE 5A CIRCUIT BREAKER WITH ON OFF SWITCH ARE TO BE SUPPLIED BY CUSTOMER MANUAL AUTOMATIC FIRE SUPPRESSION SYSTEM UPON SYSTEM DISCHARGE SHUT DOWN ENGINE FORCED VENTILATION ELECTRICAL SYSTEMS FOR MANUAL OPERATION REMOVE PIN PULL HANDLE F I R E PN 136 XXX SMAC PULL CABLE 5A CIRCUIT BREAKER WITH ON OFF SWITCH 5A CIRCUIT BREAKER WITH ON OFF SWITCH 5A ...

Page 9: ...USTOMER 5A CIRCUIT BREAKER WITH ON OFF SWITCH 5A CIRCUIT BREAKER WITH ON OFF SWITCH 5A CIRCUIT BREAKER WITH ON OFF SWITCH PN 124 LPS CYLINDER SUPERVISORY SWITCH SPST BLACK RED PN 124 969 OR PN 124 914 HORN STROBE P N 131 311 DISCHARGE PRESSURE SWITCH DPDT NOTE THIS WIRING SCHEMATIC IS A REFERENCE EXAMPLE ONLY CUSTOMER SPECIFIC WIRING SCHEMATIC MAY APPLY PER CUSTOM CONFIGURATION DIAGRAMS ...

Page 10: ... ISO 9001 registered company is fully committed to exceeding our Customer s expectations ONE YEAR LIMITED WARRANTY We guarantee to the original retail purchaser of the Sea Fire Machinery Shutdown Restart System for a period of one 1 year after retail purchase against defective material and faulty workmanship Any Engine Interrupt System found to be defective during the warranty period will be repla...

Page 11: ...Page 11 of 11 123 652 Rev ...