background image

 

Page 5 of 11

   

123-652 Rev - 

 

 
Compatible Display Panels:
 “Fire Suppression System Monitor and Engine Shutdown Control” 
          

 

Part Number 

Display Panel indicators and shape 

131-460    

Power and Discharge Indication, Rectangle 

131-461    

Power and Discharge Indication, Round 

131-462    

Power, Discharge, and High Temp Indication, Rectangle 

131-463    

Power, Discharge, and High Temp Indication, Round 

131-464    

Power, Discharge, and Aux Zone Indication, Rectangle 

131-465    

Power, Discharge, and Aux Zone Indication, Round 

131-466    

Power, Discharge, and Low-Pressure Indication, Rectangle 

131-467    

Power, Discharge, and Low-Pressure Indication, Round 

 

3.3.1.5

 

Multiple Cylinder Supervisory Switch Connection to the MSRS PS1  

 

When connecting more than one pre-engineered cylinder supervisory pressure switch to the MSRS Unit, 
connect all the supervisory pressure switches in series.  Connect the leading switch wire to Terminal 
marked “1” and the trailing wire of the last pressure switch to Terminal marked “2” (See Figure 2).   

 

 

When connecting more than one Engineered System cylinder supervisory switch to the MSRS unit, connect 
all the cylinder supervisory switches in series.   Connect the leading switch wire to Terminal marked “3” 
and the trailing wire of the last pressure switch to Terminal marked “4” (See Figure 2).   
 

 

When connecting more than one Engineered System discharge pressure switch, reference the engineered 
fire suppression manual and electrical circuit diagram provided as part of the system.   

 

3.3.1.6

 

Engine or Machinery connection 

 

Refer to the Original Equipment Manufacturers (OEM) Engine or the machinery Installation manual for the 
correct method of connection to relays of the MSRS unit.  Equipment manufacturers have a variety of 
methods to control their equipment. 

 

The following section provides the basic operation of the relays in the MSRS unit.   
 

 

4

 

Relay Operation: 
This section provides the basic operation of the relays in the ESRS unit.   

 

4.1.

 

Relay Contact Specification 

 

Table 1 Relay Contact Specification 

Item 

Value  

Contact 

SPDT (1 Form C) 

Contact Current  

10A NC / 20A NO 

Contact Voltage VAC  (Maximum allowable)  277VAC 

 

 

N/C – Normally Closed Contact 

 

N/O – Normally Open Contact 

 

COM – Common Terminal 

 
 

4.2.

 

Relay De-Energized State 

When the MSRS is operational and in the standby mode, all the relays should be in the de-energized state.   

 

The N/C and the COM terminals are connected.   

 

The N/O terminal is open.   

 
 
 

Summary of Contents for 131-740

Page 1: ... Sea Fire automatic and manual Fire Suppression Systems Installation must be accomplished by or under the supervision of a qualified marine electrician who is familiar with American Boat and Yacht Council ABYC or other recognized and accepted marine standards and practices Caution Do not install this device in fuel storage compartments See the installation section of this manual for further detail...

Page 2: ...reset function 2 OPERATION The Machinery Shutdown Restart unit is a low voltage microcontroller unit designed to integrate with the Sea Fire Fire Suppression System to shut down the engine s blower s generator s damper s and other machinery in the protected space should fire or extreme overheating cause the Sea Fire automatic Fire suppression system to discharge The machinery shutdown will ensure ...

Page 3: ...led in a box or cabinet the enclosure should have sufficient ventilation When installed in the engine room the MSRS should be installed with sufficient protection from the hazards of that space but must still have a way to dissipate heat and not be overheated by other sources WARNING Do not install the MSRS Unit in a sealed enclosure 3 2 Mounting the MSRS Unit Use the MSRS unit 4 mounting screw ho...

Page 4: ...l open activating the early warning alarm o Temperature Sensor When the temperature in the protected zone goes above the fixed temperature of the sensor the sensor shall open activating the early warning alarm 3 3 1 3 Power Supply Terminals Main Supply Backup Supply and Generator The MSRS Unit has 3 diode protected inputs but only one power source is needed to operate the MSRS and should be connec...

Page 5: ...l the cylinder supervisory switches in series Connect the leading switch wire to Terminal marked 3 and the trailing wire of the last pressure switch to Terminal marked 4 See Figure 2 When connecting more than one Engineered System discharge pressure switch reference the engineered fire suppression manual and electrical circuit diagram provided as part of the system 3 3 1 6 Engine or Machinery conn...

Page 6: ...down the alarm should sound and the red PS1 LED on the MSRS Unit should illuminate as well as the red Discharge LED on the Display Panel 6 Press the SILENCE button on the Display Panel or on the MSRS Unit to silence the alarm 7 With the PS1 circuit still open put the MSRS into override by simultaneously pressing the SILENCE and the buttons on display panel a The connected machinery should be able ...

Page 7: ... is not making good contact with the terminals Recycle power to the MSRS unit Remove and re install jumper The MSRS has an internal fault Recycle power to the MSRS unit Replace the MSRS unit 4 The PS1 and the PS2 LED are on the Alarm does not silence AND the unit does not reset The MSRS has an internal fault Replace the MSRS unit 5 The SILENCE button on the MSRS unit does not silence the alarm The...

Page 8: ...C MAY APPLY PER CUSTOM CONFIGURATION DIAGRAMS NOTE THE 5A CIRCUIT BREAKER WITH ON OFF SWITCH ARE TO BE SUPPLIED BY CUSTOMER MANUAL AUTOMATIC FIRE SUPPRESSION SYSTEM UPON SYSTEM DISCHARGE SHUT DOWN ENGINE FORCED VENTILATION ELECTRICAL SYSTEMS FOR MANUAL OPERATION REMOVE PIN PULL HANDLE F I R E PN 136 XXX SMAC PULL CABLE 5A CIRCUIT BREAKER WITH ON OFF SWITCH 5A CIRCUIT BREAKER WITH ON OFF SWITCH 5A ...

Page 9: ...USTOMER 5A CIRCUIT BREAKER WITH ON OFF SWITCH 5A CIRCUIT BREAKER WITH ON OFF SWITCH 5A CIRCUIT BREAKER WITH ON OFF SWITCH PN 124 LPS CYLINDER SUPERVISORY SWITCH SPST BLACK RED PN 124 969 OR PN 124 914 HORN STROBE P N 131 311 DISCHARGE PRESSURE SWITCH DPDT NOTE THIS WIRING SCHEMATIC IS A REFERENCE EXAMPLE ONLY CUSTOMER SPECIFIC WIRING SCHEMATIC MAY APPLY PER CUSTOM CONFIGURATION DIAGRAMS ...

Page 10: ... ISO 9001 registered company is fully committed to exceeding our Customer s expectations ONE YEAR LIMITED WARRANTY We guarantee to the original retail purchaser of the Sea Fire Machinery Shutdown Restart System for a period of one 1 year after retail purchase against defective material and faulty workmanship Any Engine Interrupt System found to be defective during the warranty period will be repla...

Page 11: ...Page 11 of 11 123 652 Rev ...

Reviews: