4.3

 

Relay Energized State  
When the MSRS is operational and is in the shutdown state, all the relays should be in the energized state.   

 

The N/C terminal is open. 

 

The N/O and the COM terminals are connected. 

 

4.4

 

Relay 20 Second Reset 

Automatic reset timer functions are optional in the MSRS.  Please contact Sea-Fire Marine for additional 
information regarding the setting of the relay 20 second timer. 

 
 
5

 

INSTALLATION CHECK 

 

1.

 

Check that all the Machinery wires installed in the MSRS terminal blocks are correct and secure as described 
above and from the machinery’s installation manuals.    

2.

 

Apply power to the MSRS.  The Green Power LED on the MSRS Unit and Display Panel should illuminate. 

3.

 

Start vessel engine(s) and all other machinery connected to / controlled by the MSRS. 

4.

 

Press the “

” Dimmer Button on the Display Panel and the Green Power LED intensity on the panel and the 

MSRS Unit shall change.  Press again to return to full brightness. 
 

5.

 

Open the “PS1” circuit loop.  The relays should energize, all connected machinery should shut down, the alarm 
should sound and the red “PS1” LED on the MSRS Unit should illuminate as well as the red Discharge LED on the 
Display Panel.   
 

6.

 

Press the “SILENCE” button on the Display Panel or on the MSRS Unit to silence the alarm. 

7.

 

With the PS1 circuit still open, put the MSRS into override by simultaneously pressing the “SILENCE” and the “

” 

buttons on display panel.   
a.

 

The connected machinery should be able to be restarted. 

b.

 

The red Discharged LED on the Display Panel and the red PS1 LED on the MSRS unit will remain illuminated. 

8.

 

Reset the unit by closing the PS1 circuit loop and simultaneously press the “SILENCE” and the “

” buttons.   

9.

 

The Green power LED on display panel and MSRS Unit should be the only LEDs lit. 

 
 

The PS2 circuit: 

1.

 

If applicable, open “PS2” circuit. The alarm should sound and both the “PS2” LED on the MSRS Unit and the Second 
Zone (Low Pressure, High Temp or Aux Discharge) LED on the Display Panel should illuminate.  The Relays should 
remain in the de-energized state.   

2.

 

Reset the unit by closing the PS2 circuit and simultaneously press the “SILENCE” and the “

” buttons. 

3.

 

The green POWER LED on the Display panel and the MSRS unit should be the only LEDs lit. 

4.

 

Use one of the Display Panels in a multiple Display Panel chain to reset the MSRS unit.     

 
 
 
 
 
 
 
 
 
 

Summary of Contents for 131-740

Page 1: ... Sea Fire automatic and manual Fire Suppression Systems Installation must be accomplished by or under the supervision of a qualified marine electrician who is familiar with American Boat and Yacht Council ABYC or other recognized and accepted marine standards and practices Caution Do not install this device in fuel storage compartments See the installation section of this manual for further detail...

Page 2: ...reset function 2 OPERATION The Machinery Shutdown Restart unit is a low voltage microcontroller unit designed to integrate with the Sea Fire Fire Suppression System to shut down the engine s blower s generator s damper s and other machinery in the protected space should fire or extreme overheating cause the Sea Fire automatic Fire suppression system to discharge The machinery shutdown will ensure ...

Page 3: ...led in a box or cabinet the enclosure should have sufficient ventilation When installed in the engine room the MSRS should be installed with sufficient protection from the hazards of that space but must still have a way to dissipate heat and not be overheated by other sources WARNING Do not install the MSRS Unit in a sealed enclosure 3 2 Mounting the MSRS Unit Use the MSRS unit 4 mounting screw ho...

Page 4: ...l open activating the early warning alarm o Temperature Sensor When the temperature in the protected zone goes above the fixed temperature of the sensor the sensor shall open activating the early warning alarm 3 3 1 3 Power Supply Terminals Main Supply Backup Supply and Generator The MSRS Unit has 3 diode protected inputs but only one power source is needed to operate the MSRS and should be connec...

Page 5: ...l the cylinder supervisory switches in series Connect the leading switch wire to Terminal marked 3 and the trailing wire of the last pressure switch to Terminal marked 4 See Figure 2 When connecting more than one Engineered System discharge pressure switch reference the engineered fire suppression manual and electrical circuit diagram provided as part of the system 3 3 1 6 Engine or Machinery conn...

Page 6: ...down the alarm should sound and the red PS1 LED on the MSRS Unit should illuminate as well as the red Discharge LED on the Display Panel 6 Press the SILENCE button on the Display Panel or on the MSRS Unit to silence the alarm 7 With the PS1 circuit still open put the MSRS into override by simultaneously pressing the SILENCE and the buttons on display panel a The connected machinery should be able ...

Page 7: ... is not making good contact with the terminals Recycle power to the MSRS unit Remove and re install jumper The MSRS has an internal fault Recycle power to the MSRS unit Replace the MSRS unit 4 The PS1 and the PS2 LED are on the Alarm does not silence AND the unit does not reset The MSRS has an internal fault Replace the MSRS unit 5 The SILENCE button on the MSRS unit does not silence the alarm The...

Page 8: ...C MAY APPLY PER CUSTOM CONFIGURATION DIAGRAMS NOTE THE 5A CIRCUIT BREAKER WITH ON OFF SWITCH ARE TO BE SUPPLIED BY CUSTOMER MANUAL AUTOMATIC FIRE SUPPRESSION SYSTEM UPON SYSTEM DISCHARGE SHUT DOWN ENGINE FORCED VENTILATION ELECTRICAL SYSTEMS FOR MANUAL OPERATION REMOVE PIN PULL HANDLE F I R E PN 136 XXX SMAC PULL CABLE 5A CIRCUIT BREAKER WITH ON OFF SWITCH 5A CIRCUIT BREAKER WITH ON OFF SWITCH 5A ...

Page 9: ...USTOMER 5A CIRCUIT BREAKER WITH ON OFF SWITCH 5A CIRCUIT BREAKER WITH ON OFF SWITCH 5A CIRCUIT BREAKER WITH ON OFF SWITCH PN 124 LPS CYLINDER SUPERVISORY SWITCH SPST BLACK RED PN 124 969 OR PN 124 914 HORN STROBE P N 131 311 DISCHARGE PRESSURE SWITCH DPDT NOTE THIS WIRING SCHEMATIC IS A REFERENCE EXAMPLE ONLY CUSTOMER SPECIFIC WIRING SCHEMATIC MAY APPLY PER CUSTOM CONFIGURATION DIAGRAMS ...

Page 10: ... ISO 9001 registered company is fully committed to exceeding our Customer s expectations ONE YEAR LIMITED WARRANTY We guarantee to the original retail purchaser of the Sea Fire Machinery Shutdown Restart System for a period of one 1 year after retail purchase against defective material and faulty workmanship Any Engine Interrupt System found to be defective during the warranty period will be repla...

Page 11: ...Page 11 of 11 123 652 Rev ...

Reviews: