WARNING

CONCENTRATED AGENT AND BY-PRODUCT OF APPLICATION TO FIRE ARE TOXIC.
AVOID BREATHING OF FUMES OR PROLONGED EXPOSURE. ACCIDENTAL DIS-
CHARGE MAY OCCUR DURING HANDLING OR INSTALLATION OF THIS DEVICE, READ
AND COMPLY WITH INSTRUCTIONS, WARNINGS, AND LIMITATIONS CONTAINED IN
THIS MANUAL. DO NOT LIFT, CARRY, OR HANDLE BY VALVE. DO NOT DROP. KEEP
AWAY FROM HEAT. KEEP AWAY FROM CHILDREN.

APPLICATION

FM-200

®

 (CF3CHFCF3), the extinguishing agent, used in all Sea-Fire “FT’’ series fire extin-

guishers, is a suitable EPA accepted alternate replacement for Halon. FM-200

®

 is electrically

nonconductive and residue free extinguishing agent that requires no cleanup.

These features and the versatility of design make the “FT’’ series fire extinguisher ideal for a
broad range of applications. The systems are ideal for small volumes, 150 cubic feet or less,
that are difficult to access. These applications would include marine, recreational vehicles,
commercial and industrial use where flammable liquids are likely source of fire.

Application Examples:
• Engine Compartments (maximum 150 cubic feet)
• Bow Thrusters
• Small Generator Set Enclosures
• Consoles
• Electrical Enclosures
• Flammable Liquid Storage Areas
• Pump Enclosures
• Alternative Fuel Storage Areas

Sea-Fire “FT” extinguishers are designed to induce a minimum atmospheric concentration of
10.0% within the protected compartment.* The specification table in this manual lists the
minimum and maximum approved compartment volume (size) allowable for each model.
Volume can be determined by multiplying the compartment’s length x width x height which
equals the volume in cubic feet or meters (LxWxH=V).

Exception: If the boat manufacturer has placed a permanently affixed label in the compart-
ment specifying the gross volume less the volume of permanently installed tankage, then
this volume may be used to determine the proper size extinguisher. Check specification table
for proper application before making installation.

*Reference: NFPA-2001 National Fire Protection Assoc. Boston, MA and UL 2166

Underwriters laboratories

SEA-FIRE “FT” SERIES AUTOMATIC FIRE SUPPRESSION SYSTEMS

FT — STINGER SPECIFICATION TABLE

AREA OF

FM-200 @

DIAMETER X

MODEL

PROTECTION

240 PSI

HEIGHT

TUBE PART # / LENGTH

CU.FT.

CU.M.

AUTO

AREA

AREA

LBS.

KG

INCH

MM

PART#

FT.

MM

FT-25

25

0.7

1.25

0.56

3.0 X 11.2

76 X 285

130-121

10

3000

FT-50

50

1.4

2.50

1.13

3.1 X 13.5

78 X 342

130-121

10

3000

FT-75

75

2.1

3.75

1.70

3.1 X 16.5

78 X 419

130-121

10

3000

FT-100

100

2.8

5.00

2.26

3.5 X 17.5

89 X 444

130-122

15

4500

FT-125

125

3.5

6.25

2.83

4.1 X 17.0 104 X 432

130-122

15

4500

FT-150

150

4.2

7.50

3.40

5.2 X 19.0 132 X 482

130-122

15

4500

CU. FT. = Cubic Feet

FT. = Feet

KG = Kilograms

CU.M. = Cubic Meters

LBS. = Pounds

MM = Millimeters

CAUTION: NEVER INSTALL A UNIT WITH A VOLUME RATING LESS THAN THE GROSS
VOLUME OF THE COMPARTMENT TO BE PROTECTED. DO NOT DEDUCT FOR
ENGINES, REMOVABLE TANKS OR OTHER EQUIPMENT.

2

Summary of Contents for FM200

Page 1: ... MUST BE INSTALLED AND MAINTAINED ACCORDINGLY READ AND COMPLY WITH THESE INSTRUCTIONS WARNINGS AND LIMITATIONS BEFORE INSTALLING SUITABLE FOR USE FT MODELS 32 F 130 F 0 C 54 C ALWAYS MAINTAIN THIS OWNER S MANUAL NEARBY FOR OPERATOR REFERENCE APPROVALS FACTORY MUTUAL FM 3022058 U S COAST GUARD U S C G 162 029 241 REV A PRINTED IN USA PART NO 123 186 ...

Page 2: ...ed compartment The specification table in this manual lists the minimum and maximum approved compartment volume size allowable for each model Volume can be determined by multiplying the compartment s length x width x height which equals the volume in cubic feet or meters LxWxH V Exception If the boat manufacturer has placed a permanently affixed label in the compart ment specifying the gross volum...

Page 3: ...ment electric supply etc When using the pressure switch as an electrical disconnect for any equipment shutdown function a means of overriding bypassing shunting the pressure switch must be provided in order to return the affected equipment to an operational mode after extinguisher discharge has occurred The pressure switch is a single pole single throw SPST type that is normally closed NC with the...

Page 4: ...ERSIDE OF COVER OR COM PARTMENT HATCH THAT COULD BE THROWN CLEAR DUE TO POSSIBLE EX PLOSION 8 DO NOT MOUNT WHERE AN ACCUMULATION OF STANDING WATER COULD BLOCK SENSOR OR CAUSE CORROSION 9 EXTINGUISHER TO BE MOUNTED IN THE VERTICAL POSITION ONLY 10 DO NOT USE FOR PRIMARY ENGINE COMPARTMENT PROTECTION EXTINGUISHER INSTALLATION Step 1 Carefully remove extinguisher from carton and visually check for da...

Page 5: ...ssembly Note Do not kink tub ing if kink occurs remove effected area with razor Step 10 Tighten fitting and tube to cylinder using 1 2 12mm wrench Preferred torque value is 3 4 1 2 inch pounds of force Overtightening may cause tube to rupture Step 11 Activate system Using a straight screwdriver open valve VERY SLOWLY counter clockwise 1 4 of a turn to allow detection tube to fill with nitrogen Not...

Page 6: ...oper range 2 Check fuse and indicator light and replace if defective lamp replacements available from factory 3 Check for loose electrical connections 4 Remove and weigh system cylinder as described in MAINTENANCE Section of the manual INDICATOR LIGHT INSTALLATION Select a location at the helm on or near the console that is in full view of the helmsman the location selected must have access for el...

Page 7: ...nd tools Attach one wire lead from the in line fuse to the ignition position on the starter switch Connect other lead from the in line fuse to the indicator light Connect remaining indica tor lead to one of the Sea Fire cylinder pressure switch connector wires Connect the remaining cylinder pressure switch lead to common ground which may be the negative battery buss at the control panel or directl...

Page 8: ... audible system status indicator with override switch for engine restart Avail able with 3 5 or 8 control circuits in 12 or 24 VDC models ESRS WT III V VIII Same as ESRS MARK shutdown system but also includes a factory installed nominal 20 second release timer on the engines control cir cuits For use in diesel engines that shutdown through activation of a momentary device i e push button lever etc...

Page 9: ...ystem for one half of the current suggested list price RETURN TO UNITED STATES EUROPE SEA FIRE MARINE SEA FIRE EUROPE LTD Division of Metalcraft Inc Unit 7 io Centre Stephenson Road 9331 A Philadelphia Road Fareham Hampshire Baltimore Maryland 21237 USA PO15 5RU United Kingdom Website www sea fire com EQUIPMENT LIST FOR INSTALLATION 1 Drill motor 2 Drill bit 25 64 390 for rubber grommet 3 Drill bi...

Page 10: ...MPERATURE RANGE 32 F 130 F 0 C 54 C STANDARD EQUIPMENT LIST SUPPLIED WITH EACH SYSTEM 1 ONE TUBING KIT PART 130 121 10 FOOT TUBE OR 130 122 15 FOOT TUBE 2 ONE BRACKET ASSEMBLY Model Bracket Part FT 25 122 010 FT 50 122 010 FT 75 122 010 FT 100 130 011 FT 125 130 012 FT 150 130 013 10 ...

Page 11: ... property damage if the valve is broken due to improper handling or storage Section 4 First Aid Measures Skin contact Flush with water treat for frostbite if necessary by gently warming affected areas Consult a physician Eye contact Immediately flush eyes with plenty of water for at least 15 minutes Consult an ophthalmologist Inhalation Remove victim s to fresh air as quickly as possible If not br...

Page 12: ...nimal Routes Components 788 696 ppm 4H Rat Acute Inhalation 1 1 1 2 3 3 3 Heptafluoropropane The human health hazards of this product are expected to be similar to other liquefied gases including N2 C02 CFCs HCFCs and HBFCs Therefore direct eye or skin contact with the liquid or cold gas can cause chilling or possibly frostbite of exposed tissues Inhalation of high concentrations can be harmful or...

Page 13: ... DISCLAIMER OF EXPRESSED AND IMPLIED WARRANTIES Metalcraft Sea Fire Marine Inc has taken reasonable care in preparing this document how ever since the use of this information and the conditions of use of the product are not within the control of Metalcraft Sea Fire Marine Inc it is the user s obligation to determine the conditions of safe use of this product The information in this document is off...

Page 14: ...MARINE SEA FIRE EUROPE LTD Division of Metalcraft Inc Unit 7 io Centre Stephenson Road 9331 A Philadelphia Road Fareham Hampshire Baltimore Maryland 21237 USA PO15 5RU United Kingdom Website www sea fire com 14 ...

Reviews:

Related manuals for FM200