Ultra Whisper 400-600
During start up, the current of the Feed Water Pump Alternating Current Ele
ctric Motor surges to “Locked Rotor”
or “Starting Amps” amperage for a fraction of a second after which the Electric Motor begins to rotate. After the
Electric Motor achieves full RPM rotation the current drops to normal running load. This process will take less than
1/2 second.
Therefore, the maximum surge current that the power source must be able to deliver equals the Feed Water Pump
Electric Motor starting amperage listed in the Specification Chapter of this manual. If the AC Power Source (AC
Generator or Dock Power) is insufficient the Ultra Whisper Electric Motor will not gain the full RPM speed needed
for it to switch to running amperage mode, will consume “starting amps” amperage continually, and will either trip
the power source circuit breaker or overheat and short out. Similar results will occur if the Frequency (Hz or Cycles)
drop below the minimum requirement, which will occur from a weak AC Generator that slows down when a load is
applied to it. This is an installation problem (insufficient power supply), it is not an Ultra Whisper problem.
Direct Current Powered Systems:
During start up, the current of the Feed Water Pump Direct Current Electric Motor draws high amperage for a
fraction of a second after which the Electric Motor begins to rotate. After the Electric Motor achieves full RPM
rotation the current drops to normal running load. This process will take less than 1/2 second.
Therefore, the battery bank power source must be fully charged and of sufficient amperage storage capacity to
provide and maintain the full voltage (12 VDC or 24 VDC as appropriate) at the instant of starting the Feed Water
Pump Electric Motor. If the battery bank power is insufficient the Ultra Whisper electronic circuit may “drop out”
due to power loss before the Electric Motor even begins to rotate. This is an installation problem (insufficient power
supply), it is not an Ultra Whisper problem. Low DC voltage to the Feed Pump electric motor will also be caused by
insufficient diameter power cables connected from the b
attery bank, through the boat’s circuit breaker, and on to
the Ultra Whisper controller.
Power Source Requirements:
Check line voltage and frequency to ensure that it agrees with the system nameplate. Grounding and circuit
protection should be done in accordance with National Electrical Code. See connection diagram on nameplate of
motor or refer to the diagrams within this manual.
Voltage
HZ (AC)
Min. HZ
Max. HZ
Min. Voltage
Max. Voltage
DC Systems
12 VDC
N/A
N/A
N/A
11 VDC
15 VDC
24 VDC
N/A
N/A
N/A
22 VDC
30 VDC
AC Systems
120 VAC
60 HZ
57 Hz
62 Hz
108 VAC
132 VAC
230 VAC
60 HZ
58 Hz
62 Hz
207 VAC
253 VAC
100 VAC
50 HZ
48 Hz
52 Hz
90 VAC
110 VAC
220 VAC
50 HZ
48 Hz
52 Hz
198 VAC
242 VAC
Feed Pump Motor Electrical Specification
12 and 24 VDC
UW 400
12V / 24V
UW 600
24V
Nominal Operating Amps
21/10.5
3
3
/1
6.5
Maximum Motor Amps
28/13.4
39/19.5
Starting Amps
4
5
/
22.5
65
/
32.5
Horse Power
0.3
0.5
Recommended Circuit Breaker
5
0
/
25
70
/
35
Minimum Size Power Wire AWG
6/8
6/8
Electrical Information
66
Summary of Contents for Ultra Whisper Compact 400
Page 2: ......
Page 3: ...Ultra Whisper 400 600 Owner s Manual Manual PN B651380001D...
Page 4: ......
Page 8: ......
Page 18: ...1 6 UltraWhisper400 600...
Page 24: ...22 UltraWhisper400 600...
Page 36: ......
Page 37: ......
Page 38: ......
Page 48: ...46 UltraWhisper400 600...
Page 58: ......
Page 59: ......
Page 60: ......
Page 66: ...Ultra Whisper 400 600 64...
Page 71: ...Chapter 12 Exploded Parts View 69...
Page 81: ...79 7 8 6 4 1 3 1 2 4 9 5...
Page 97: ...95 Exploded Parts View 6 7 5 2 3 2 4 10 5 8 9 1...
Page 99: ...12 8 9 2 10 13 1 3 5 4 14 11 6 15 7 97...
Page 105: ...Chapter 13 Appendix 103...
Page 106: ......
Page 107: ......
Page 108: ......
Page 109: ......
Page 110: ......
Page 111: ......
Page 113: ......
Page 118: ......
Page 119: ......
Page 120: ......