INSTALLER/CONFIGURATION MENU (CONTINUED.)
9
PROG
(
)
,
Selects time format displays 12 or 24 hour
10
PROG
(
)
,
Selects compressor delay OFF or ON
11
PROG
(
)
,
Selects stages turn off sequence (COmfort or EConomy)
12
PROG
( )
,
(1 =) Programmable (0 =) Non-Programmable (Selectable)
13
PROG
(
)
-
Communication channels
14
PROG
( )
,
Set to 1 to match transmitter to receiver.
15
PROG
( )
,
0 = Only change temperature, 1 = All functions locked.
16
PROG
(
)
,
Activates economy operation (step 17 and 18)
17
PROG
(
° )
-
° (5-34°C)
Select economy heat setting between 41-93°F (5-34°C)
18
PROG
(
° )
-
° (6-35°C)
Select economy cool setting between 43-95°F (6-35°C)
19
PROG
(
° )
-
° (-2-35°C)
Select compressor lock out mode between 28-95°F (-2-35°C)
20
PROG
( )
, ,
0=no test, 1=1 stage test, 2=2 stage test
21
PROG
( )
0 = new configuration, 1= return to factory defaults
Step 1) Factory default is
“
”
Selects SINGLE STAGE, MULTI-STAGE or HEAT PUMP (1 stage or 2 stages) system configuration.
The configuration can be toggled to select one to four systems by pressing the
▲ or ▼ buttons. In HEAT PUMP configuration
only, EMER mode is available.
Selection for systems:
“
” – Single stage (Cool or Heat)
“
” – Multi-Stage (2 - Cool and 2 - Heat)
“
” – Heat Pump system (1 – Cool and 2 – Heat)
“
” – Heat Pump system (2 – Cool and 3 – Heat)