background image

 4.  PREPARATION

4.1.

 

Remove compressor from packaging and inspect for any shortages or damage. If anything is found to be missing or damaged contact  

 

your supplier.

4.2.

 

Save the packing material for future transportation of the compressor.  We recommend that the packing is stored in a safe location, at  

 

least for the period of the guarantee. Then, if necessary, it will be easier to send the compressor to the service centre.

4.3.

 

Confirm that the mains voltage corresponds with the voltage shown on the compressor data plate.

4.4.

 

SAC05030.V2- Fit the main wheels (fig.1.A) and two rubber feet (fig.1.B) to the main frame using the nuts, bolts and washers supplied.

 

SAC10030.V2- Fit the main wheels (fig.1.D) and small wheel (fig.1.E) to the main frame using the nuts, bolts and washers supplied.

4.5.

 

The compressor should be installed on a flat, firm surface, or one that does not exceed 15

°

 either transversely or longitudinally, and    

   

should be in a position that allows good air circulation around the unit.

4.6.

 

The compressor is shipped with oil in the pump, but the level needs checking before starting the unit for the first time. Check the oil level by  

 

referring to the oil sight glass (fig.2.B). If the oil level is not up to the red centre mark, it should be topped up. Remove the plastic  

 

 

transit plug from the oil filler hole and if required, pour in the recommended oil. (See section 5.6). Screw the filler/breather cap  

 

 

supplied into the aperture as shown (fig.2.A).

 5.  OPERATION

  

WARNING! 

Ensure that you have read, understood and apply Section 1 safety instructions.

5.1.

  

IMPORTANT.  

The use of extension leads to connect this compressor to the mains is not recommended as the resulting voltage drop  

 

reduces motor, and therefore pump, performance.

5.2.  

Take care when selecting tools for use with the compressor. Air tool manufacturers normally express the volume of air required to    

 

operate a tool in cubic feet per minute (cfm). This refers to free air delivered by the compressor (‘air out’) which varies according to the  

 

pressure setting. Do not confuse this with the compressor displacement which is the air taken in by the compressor (‘air in’). ‘Air out’ is  

 

always less than ‘air in’ - due to losses within the compressor.

5.3. 

STARTING THE COMPRESSOR.

5.3.1.  The compressor is fitted with a push/pull type of ON/OFF switch (fig.3.A). 

 

To turn the compressor ‘ON’ pull the switch knob upwards. To turn the    

 

 

compressor ‘OFF’ push the switch knob downwards.

5.3.2.  Check that the ON/OFF switch is in the “OFF” position and the regulator tap  

 

 

(fig.3.C) is closed (Zero ‘0’ bar, Anti-clockwise).

 

   

5.3.3.  Plug mains lead into mains supply and start the compressor by pulling the  

 

 

ON/OFF switch knob upwards.

5.3.4. Leave the compressor running with the regulator tap (fig.3.C) set to maximum  

 

 

pressure. Make sure that the pressure in the tank rises and that the compressor  

 

 

stops automatically when the maximum pressure value allowed - written on the  

 

 

specification plate and shown on the gauge (fig.3.G) - is achieved.  

 

 

 

The compressor will now operate automatically. The pressure switch (fig.3.B) stops  

 

the motor when the maximum tank pressure is reached, and will restart it when  

 

 

pressure falls below the minimum threshold - approx. 2 bar (29psi) less than the  

 

 

maximum pressure.

5.3.5.  Stop the compressor by pushing the switch knob downwards (fig.3.A). The   

 

 

compressed air inside the compressor head will exhaust, making the restart easier  

 

and preventing the motor from being damaged. 

 

DO NOT

, other than in an emergency, stop the compressor by switching off the mains socket, or by pulling the plug out of the socket,  

 

as the pressure relief will not then occur and motor damage may result upon restart.

 

When the compressor runs correctly and is stopped correctly there will be:

  

(a)

 a whistle of compressed air when the motor stops,

  

(b)

 a protracted whistle (about 20-25 seconds) when the compressor starts with no pressure in the tank.

5.3.6.  The output pressure is regulated by the pressure regulator tap (fig.3.C). Turn the tap clockwise to increase pressure and anti-clockwise to    

 

reduce it. The tap can be locked at any required setting by tightening the locking ring (fig.3.D) up against the underside of the tap.    

 

To determine the correct working pressure for any piece of equipment check the corresponding manual. When the compressor is not   

 

being used, set the regulated pressure to zero so as to avoid damaging the pressure reducer.

NOTE:   a)

 If the motor does not cut in and out, but runs continuously when using an air appliance, the capacity of the compressor may be too  

 

  small for the equipment or tool.

 

b)

 The larger gauge (fig.3.G) indicates the pressure inside the main tank. The smaller gauge (fig.3.F) indicates the pressure supplied to  

 

  the air equipment. Should the pressure in the main tank exceed the pre-set switch (fig.3.B) maximum, the safety valve (fig.3.H) will   

 

 activate. 

 

WARNING! For this reason DO NOT tamper with, or adjust, the pre-set switch or safety valve (fig.3.B&H). 

5.3.7.  The compressor is fitted with an overload switch, and a reset trip button located in the connection box on top of the motor 

 

(see fig.1.C & fig.6). Should the overload switch activate, switch the compressor off and leave for a few minutes before pressing the    

 

trip reset button to reset, and then re-start the compressor. For possible causes of overload switch activation and remedies, see  

 

 

Section 6.

fig.3

 6.  MAINTENANCE

 

In order to keep the compressor in good working condition, periodic maintenance is essential.

 

WARNING!

 Before performing any maintenance operation, switch off the compressor, disconnect from electrical supply and  

 

 

release all air from the tank.

 

IMPORTANT! Failure to carry out maintenance tasks may invalidate the warranty on your compressor.

6.1.   Operations to be carried out after the first 5 working hours:

 

a)

 Check that all nuts/bolts are tight, particularly those retaining the crankcase and cylinder heads.

6.2.   Operations to be carried out after the first 100 working hours:

 

a)

 Replace the lubricating oil (see 6.6. below).

 

6.3. 

Operations to be carried out daily:

 

 

a)

 Drain condensation by opening the valve located under the tank (fig.4). Place a container under the valve to collect any   

 

 

   condensation, as it may contain residual oil. Close valve after draining condensation and dispose of it safely.

 b)

 Regularly clean dirt and dust away from the safety devices with a clean cloth or by blowing with low pressure compressed air.  

 

 

    Generally keep the compressor clean. 

SAC05030.V2, SAC10030.V2  Issue: 2 (L) -15/08/18

Original Language Version

 © Jack Sealey Limited

Summary of Contents for 50LTR V-TWIN

Page 1: ... NOT use worn or damaged cables plugs or connectors Immediately have any faulty item repaired or replaced by a qualified electrician When a BS 1363 A UK 3 pin plug is damaged cut the cable just above the plug and dispose of the plug safely Fit a new plug according to the following instructions UK only a Connect the GREEN YELLOW earth wire to the earth terminal E b Connect the BROWN live wire to th...

Page 2: ...ried out annually The tank shell must not fall below the certified thickness at any point Inspection of pressure tank both internal and external Under the PRESSURE SYSTEMS SAFETY REGULATIONS 2000 it is the responsibility of the owner of the compressor to initiate a system of inspection that both defines the frequency of the inspection and appoints a person who has specific responsibility for carry...

Page 3: ...elow the minimum threshold approx 2 bar 29psi less than the maximum pressure 5 3 5 Stop the compressor by pushing the switch knob downwards fig 3 A The compressed air inside the compressor head will exhaust making the restart easier and preventing the motor from being damaged DO NOT other than in an emergency stop the compressor by switching off the mains socket or by pulling the plug out of the s...

Page 4: ...h fresh oil through the oil filler breather aperture Do not overfill Replace oil filler breather plug WARNING Never mix different oils and do not use non detergent low quality oils as the compressor may be damaged Recommended oils Recommended oil for compressors suitable for temperatures ranging from 5 C to 25 C SEALEY CPO or equivalent SAE 40 compressor oil WARNING Dispose of waste oil only in ac...

Page 5: ...button Remove extension lead and test the compressor by connecting as near to the main fuse box as possible Extension lead too long Head unloader not operating Section 4 3 5 Contact Authorised Service Agent Occasionally the start up load may activate switch NOTE It is our policy to improve products continually and as such we reserve the right to alter data specifications and component parts withou...

Reviews: