background image

 

‰

   WArNiNG!

 ensure that you have read, understood and apply section 1 safety instructions. 

5.1.    

the compressor should be located and operated in a position that allows good air circulation around the unit. locate the compressor  

 

in a convenient position for the work to be undertaken. Ensure that it is standing on a stable and level surface. Ensure the feet/wheels  

 

are in direct contact with the surface.

5.2.    

Attach the required air tool to the air outlet. 

5.3. 

  

Plug the mains plug into a mains electrical socket, but do not switch the compressor on until the workpiece and air tool are fully prepared. 

 

Switch on the unit by pushing the switch to the On position (SAC00015 - Fig.1.6) or pulling the red On/Off switch upwards (Figs.2.6 &  

 

3.6). 

5.4.    

On the SAC00615 and SAC02415 models, the output pressure is regulated by the pressure regulator tap (Figs.2.3 & 3.3). Adjust the

 

pressure regulator tap to the pressure required. the tap can then be locked at the required setting by tightening the locking ring    

 

(Figs.2.2 & 3.2) behind the tap. When the compressor is not being used, set the regulated pressure to zero so as to avoid damaging  

 

the pressure reducer.

 Note:

  

a)

 On the SAC00615 and SAC02415 models, if the motor does not cut in and out, but runs continuously when using an air appliance,  

 

the capacity of the compressor may be too small for the tool being used.

 

b)

 The larger gauge (figs.2.4 & 3.4) indicates the pressure inside the main tank. The smaller gauge (fig.2.5 & 3.5) indicates the    

 

pressure supplied to the air equipment. 

The pressure switch (figs.2.7 & 3.7) stops the motor when the maximum tank pressure is    

 

reached and restarts it when pressure falls below the minimum threshold - approximately 2 bar (29psi) less than the maximum pressure.

 

‰

  

WArNiNG!

 for this reason 

do Not

 tamper with, or adjust, the pre-set switch or safety valve.

 

c)

 Should there appear to be any loss of efficiency when using the compressor, ensure first that the air tool is clean and functioning  

 

properly. If the air tool is satisfactory then refer to the Troubleshooting guide, section 7.

5.5.    

do not leave the compressor running for any length of time with the air tool attached, but not being used. if there is a pause in the  

 

work, switch the compressor off. these compressors have a duty-cycle of 25%. for each period of use, a rest period of three times  

 

that length should be left before using it again (for example: after 2½ minutes use, a rest period of 7½ minutes should follow). If the  

 

motor overheats, the thermal cut-out will operate and cut the motor out. When the temperature has returned to normal, the motor will  

 

re-start automatically.  

5.6. 

  

if the operating note of the compressor changes, there may be a blockage within the tool, or the air hose may be pinched. the    

 

unit should be switched off immediately, and the source of the blockage investigated and eliminated, before re-starting.

 

When work is complete, switch the compressor off. by pushing the switch to the Off position (SAC00015 - Fig.1.6) or pushing the red  

 

On/Off switch downwards (Figs.2.6 & 3.6). Operate the air tool to clear any pressure left in the air hose. Disconnect the air tool from  

 

the compressor. for models with air tanks, vent any pressure remaining in the tank by manually operating the safety valve (pull on the  

 

metal ring) situated next to the pressure switch assembly. open the drainage tap at the bottom of the tank, to allow any    

 

 

moisture to be drained from the tank. this prevents corrosion on the inside of the tank. close drainage tap.

5.7. 

  

if it is intended to store the compressor away, allow it to cool before storing it carefully in a safe, dry, dust free, childproof location.

6. 

 

mAiNteNANce

a

 

before carrying out any maintenance, switch compressor off, unplug it from the mains electricity supply, depressurise the tank  

 

and allow unit to fully cool down.

6.1.    

Keep the compressor clean and free of dust. Do not use cleaning agents. Wipe the compressor using a slightly dampened cloth and  

 

blow it over with compressed air. 

6.2. 

  

ensure that the ventilation openings are clear. do not allow any extraneous material to enter the unit via any of the ventilation  

 

 openings. 

6.3. 

  

to prevent corrosion to the tank, drain it on a regular basis by opening the drainage tap at the bottom of the tank, after draining ensure  

 

the drainage tap is fully closed. 

7.  troUbleshootiNG

7.1.    

the troubleshooting guide below is intended to give an indication of the type of fault which may develop with the compressor over a   

 

long period of service. the chart is not intended as a guide on how to repair the fault, it is recommended that the compressor is  

 

 

returned to an authorised service agent for rectification of serious faults.

fault

possible cause

remedy

Air leakage from the valve of the pressure 

switch whilst the compressor is off.

Pressure switch valve, due to wear or dirt 

on the seal, does not perform correctly.

unscrew the head of the valve, clean the valve seat 

and the rubber disc  (replace if worn). 

reassemble and tighten carefully.

the compressor does not stop and the safety 

valve is tripped.

reduction in performance. frequent start-up. 

low pressure values.

irregular functioning of the compressor or 

broken pressure switch. 

excessive air consumption, leaks from 

the couplings and/or pipes. 

switch off compressor and contact 

Authorised service Agent.

clean the air vents and ensure the work area is 

ventilated. do not over-run the compressor's duty 

cycle. 

Air tool requires higher spec. compressor. 

Check / replace the seals of the fitting. 

the compressor stops, then restarts 

automatically after a few minutes.

tripping of the thermal cutout due to 

overheating of the motor.

s

AC00015, SAC00615, SAC02415 | Issue:3 (I) 04/10/17

Original Language Version

© Jack sealey limited

Summary of Contents for SAC00015

Page 1: ...nal L C Connect the BLUE neutral wire to the neutral terminal N Ensure that the cable outer sheath extends inside the cable restraint and that the restraint is tight Sealey recommend that repairs are carried out by a qualified electrician 1 2 General Safety WARNING Compressor must only be serviced by an authorised agent 9 9 Familiarise yourself with the application and limitations of the compresso...

Page 2: ...lator with gauge Model no SAC02415 supplied with wheels and handle Fitted with ASTA BS approved non rewireable plug 3 specification 4 assembly 4 1 Remove compressor from packaging and inspect for any shortages or damage If anything is found to be missing or damaged contact your supplier 4 2 If wheels and or feet are not fitted to compressor fit them using the appropriate nuts bolts and washers sup...

Page 3: ... switched off immediately and the source of the blockage investigated and eliminated before re starting When work is complete switch the compressor off by pushing the switch to the Off position SAC00015 Fig 1 6 or pushing the red On Off switch downwards Figs 2 6 3 6 Operate the air tool to clear any pressure left in the air hose Disconnect the air tool from the compressor For models with air tanks...

Page 4: ...ee Regulations Dispose of this product at the end of its working life in compliance with the EU Directive on Waste Electrical and Electronic Equipment WEEE When the product is no longer required it must be disposed of in an environmentally protective way Contact your local solid waste authority for recycling information Environment Protection Recycle unwanted materials instead of disposing of them...

Reviews: