background image

5.  MAINTENANCE  

5.1.

   OPERATIONS TO BE CARRIED OUT AFTER THE FIRST 

 

5 WORKING HOURS:

 

a) Check that all bolts/nuts are tight, particularly those  

 

retaining the crank case and cylinder head.

5.2.

   OPERATIONS TO BE CARRIED OUT AFTER THE FIRST  

 

50 WORKING HOURS:

 

b) Replace the lubricating oil - see para 5.5. 

5.3.

 

OPERATIONS TO BE CARRIED OUT DAILY: 

 

a) Drain condensation by opening the valve located under  

 

the tank (fig.5). Place a container under the valve and slowly  

 

open the valve by turning anti-clockwise. 

5.4.

   OPERATIONS TO BE CARRIED OUT EVERY 100 HOURS  

 

(or more frequently, if the compressor operates in a very  

 

dusty 

atmosphere): 

    

 

a) Check oil level and, if necessary, top up.  

 

b) Remove the filter elements (See fig.4) and clean with  

 

compressed air. (Wear eye protection). 

DO NOT

 operate the  

 

compressor without the filters as foreign bodies or dust could  

 

seriously damage the pump.

 

c) Check for oil leaks

5.5.

   OPERATIONS TO BE CARRIED OUT EVERY 200 HOURS:

 

a) Replace the lubricating oil. For oil specifications see 5.7.

 

Remove the oil filler/breather plug (see fig.2.B) then unscrew  

 

oil sight glass (see fig.2.C) and drain the oil into a container. 

 

Drain when the compressor is hot so that oil drains rapidly  

 

and completely. Incline compressor to ensure complete  

 drainage. 

 

Replace oil sight glass and refill through the oil filler/breather  

 

aperture. Do not overfill. Replace filler/breather plug.

 

b) Check the automatic cut-out at max. pressure and the  

 

automatic cut-in at 2 bar below.

  

WARNING! Never mix different oils and do not use non- 

 

detergent/low quality oils as the compressor may be  

 damaged.

  

WARNING!

 

Dispose of waste oil only in accordance with  

 

local authority requirements.

 

This refers to free air delivered by the compressor (‘air  

 

out’) which varies according to the pressure setting. Do  

 

not confuse this with the compressor displacement  

 

which is the air taken in by the compressor (‘air in’). ‘Air  

 

out’ is always less than ‘air in’ - due to losses within the  

 compressor.

4.3. 

STARTING THE COMPRESSOR.

4.3.1.  Your compressor is fitted with a push/pull type of ON/OFF  

 

switch. To turn the compressor ‘ON’ pull the switch knob  

 

upwards. To turn the compressor ‘OFF’ push the knob  

 

downwards. (See fig.3.1)

4.3.2.  Check that the ON/OFF switch is in the “OFF” position, the  

 

regulator tap (fig.3.2) is closed (Zero ‘0’ bar) 

   

4.3.3.  Plug mains lead into mains supply and start the compressor  

 

by pulling the switch knob upwards.

4.3.4.  When starting the compressor for the first time, leave it  

 

running for several minutes with the drain valve (fig.5) open  

 

to ensure good distribution of the lubricating oil. Turn the  

 

compressor off and close the drain valve. Restart the  

 

compressor and leave it running with drain valve (fig.5)  

 

closed and regulator (fig.3.2) set to maximum pressure.  

 

Make sure that pressure in the tank rises and that the  

 

compressor stops automatically when the max. pressure  

 

value allowed - written on the specification plate and  

 

shown on the gauge (fig.3.5) - is achieved. The compressor  

 

will now operate automatically. The pressure switch (fig.3.7)  

 

stops the motor when the maximum tank pressure is reached  

 

and restarts it when pressure falls below the minimum  

 

threshold - approx. 2 bar (29psi) less than the maximum  

 pressure.

4.3.5.  Stop the compressor by pushing the switch knob (See fig.3.1)  

 

downwards. The compressed air inside the compressor  

 

head will flow out, making the restart easier and preventing  

 

the motor from being damaged. 

DO NOT

, other than in an  

 

emergency, stop the compressor by switching off the mains  

 

power, or by pulling the plug out, as the pressure relief will  

 

not then occur and motor damage may result upon restart.

 

When the compressor runs correctly and is stopped correctly  

 

there will be: 

 

(a) A whistle of compressed air when the motor stops,

 

(b) A protracted whistle (about 20-25 seconds) when the  

 

compressor starts with no pressure in the tank.

4.3.6.  The output pressure is regulated by the pressure regulator  

 

(fig.3.2). Turn the knob clockwise to increase pressure and  

 

clockwise to reduce it. The knob can be locked at any  

 

required setting by tightening the locking ring (fig.3.3) up  

 

against the underside of the knob. To determine the correct  

 

working pressure for any piece of equipment check the  

 

corresponding manual. When the compressor is not  being  

 

used set the regulated pressure to zero so as to avoid  

 

damaging the pressure reducer.

 

NOTE:

 a) If the motor does not cut in and out, but runs  

 

continuously when using an air appliance, the capacity of the  

 

compressor may be too small for the equipment or tool.

 

b) The larger gauge (fig.3.5) indicates the pressure inside the  

 

main tank. The smaller gauge (fig.3.4) indicates the   

 

pressure supplied to the air equipment. Should the pressure  

 

in the main tank exceed the pre-set switch (fig.3.7)    

 

maximum, the safety valve (fig.3.6) will activate. 

  

WARNING! For this reason DO NOT tamper with, or  

 

adjust, the switch or safety valve. 

4.3.7.  The compressor is fitted with a reset trip, located in the  

 

connection box on top of the motor (see fig.A.Z) The reset  

 

button is on the side of the box (fig.6). Should the trip activate,  

 

leave for 1 minute before pressing the button to reset. For  

 

possible causes of trip activation and remedies see 

 

section 6 Troubleshooting.

fig.3

 

In order to keep the compressor in good working condition,    

 

periodic maintenance is essential.

  

WARNING!

 

Before performing any maintenance operation,  

 

switch off the compressor, disconnect from electricity  

 

 

supply and release all air from the tank.

 

IMPORTANT! Failure to carry out maintenance tasks may   

 

invalidate the warranty on your compressor.

fig.4

fig.5

Original Language Version

© Jack Sealey Limited

SAC10030VE   Issue No: 2(I) - 17/04/14

fig.6

Summary of Contents for SAC10030VE

Page 1: ... insulated products which are always marked with this symbol are fitted with live brown and neutral blue wires only To rewire connect the wires as indicated in diagram DO NOT connect either wire to the earth terminal 1 1 10 Products which require more than 13A are supplied without a plug In this case you must contact a qualified electrician to ensure that a suitably rated supply is available INSTR...

Page 2: ...pply Section 1 safety instructions 4 1 IMPORTANT The use of extension leads to connect this compressor to the mains is not recommended as the resulting voltage drop reduces motor and therefore pump performance and could damage your compressor 4 2 Take care when selecting tools for use with the compressor Air tool manufacturers normally express the volume of air required to operate a tool in cubic ...

Page 3: ...to maximum pressure Make sure that pressure in the tank rises and that the compressor stops automatically when the max pressure value allowed written on the specification plate and shown on the gauge fig 3 5 is achieved The compressor will now operate automatically The pressure switch fig 3 7 stops the motor when the maximum tank pressure is reached and restarts it when pressure falls below the mi...

Page 4: ... return valve cap 3 spring 2 and seal 1 Clean the seal and its seat or if necessary replace the seal 3 Air leaks from tank body or tank welds Internal corrosion caused by infrequent tank draining or non permitted modifications to tank Tank could rupture or explode Cannot be repaired DISCONTINUE USE IMMEDIATELY 4A Motor stops and will not restart Thermal cut out has operated Allow unit to cool for ...

Reviews: