background image

4.6. 

  

To ensure good ventilation and efficient cooling, the compressor’s belt guard must be at least 100cm from any wall (fig.3).

 

Compressors with fixed feet, should not be rigidly secured to the floor. In this case, it is advised to fit 4 anti-vibration supports (optional  

 extra).

4.7.    

Take care to transport the compressor correctly, 

DO NOT

 overturn it or lift it with hooks or ropes.

4.8. 

  

Remove the plastic transit plug from the oil filler hole (fig.4) and replace it with the filler/breather plug. It is a push fit, ensure that it is   

 

pushed fully home.

4.9.    

Before using the compressor, check the oil level by observing the sight glass as shown in fig.4. If the oil is not up to the max mark it   

 

should be topped up with synthetic oil suitable for temperatures ranging from -5°C to 45°C (viscosity 5W50). We 

DO NOT

 recommend  

 

using mineral oil in these compressors.

 DO NOT 

overfill.

5.  OPERATION

 

‰

  

WARNING!

 Ensure that you have read, understood and apply Section 1

 

safety instructions.

 

IMPORTANT!

  Use of extension leads to connect these compressors to the

 

the mains is not recommended as the resulting voltage drop reduces motor

 

and therefore pump performance, and could damage the compressor.

 NOTE: 

Take care when selecting tools for use with the compressor. Air tool  

 

 

 

manufacturers normally express the volume of air required to operate a 

 

tool in cubic feet per minute(cfm).This refers to free air delivered by the  

 

 

 

compressor (‘air out’) which varies according to the pressure setting. 

 

DO NOT

 confuse this with the compressor displacement which is the air

 

taken in by the compressor (‘air in’). ‘Air out’ is always less than ‘air in’ due 

 

to losses within the compressor.

5.1.    

STARTING / STOPPING THE COMPRESSOR

5.1.1.  

To turn the compressor on use the switch on the top of the pressure switch 

 

housing (figs.6.1 and 7.1). Turn the switch clockwise to position ‘I’ to start the 

 

compressor and anti-clockwise to position ‘O’ to stop it. 

5.1.2. 

  

Check that the ON/OFF switch is in the ‘O’ position. On Models SAC1503B 

 

and SAC1103B the regulator tap (fig.6.2) should be closed and the output 

 

gauge (fig.6.4) must read Zero ‘0’ bar.

 

5.1.3.   

Plug into mains supply and start the compressor by turning the switch to the

 

 ‘I’ position.

5.1.4.   

When starting the compressor for the first time, leave it running with no air

 

tools connected to the air outlet. Make sure that pressure in the tank rises 

 

and that the compressor stops automatically when the maximum pressure 

 

value allowed - written on the plate and shown on the gauge (figs.6.5 & 7.5) - 

 

is achieved. The compressor will now operate automatically. The pressure 

 

switch stops the motor when the maximum tank pressure is reached and 

 

restarts it when the pressure falls below the minimum threshold - approx. 2 bar (29psi) less than the maximum pressure. 

5.1.5. 

  

Stop the compressor by turning the main switch to the ‘O’ position. The compressed air inside the compressor head will flow out, making  

 

the restart easier and preventing the motor from being damaged. 

DO NOT, 

other than in an emergency

,

 stop the compressor by switching  

Original Language Version

© Jack Sealey Limited

fig.1

fig.2

fig.4

fig.3

fig.7

fig.6

fig.5

SAC1503B, SAC1103B, SAC1153B, SAC1203B         Issue: 4(1, 3, 6) 30/10/18 

Summary of Contents for SAC1103B

Page 1: ...alified electrician 1 1 3 Ensure that the insulation on all cables and on the appliance is safe before connecting it to the power supply See 1 1 1 and use a Portable Appliance Tester 1 1 4 Ensure that cables are always protected against short circuit and overload 1 1 5 Regularly inspect power supply cables and plugs for wear or damage and check all connections to ensure that none is loose 1 1 6 IM...

Page 2: ...8 8 DO NOT subject the tank to impact vibration or to heat and DO NOT allow contact with abrasives or corrosives 9 9 Drain condensation from tank daily and inspect inside walls for corrosion every three months and have a detailed tank inspection carried out annually The tank shell must not fall below the certified thickness at any point WARNING If an electrical fuse blows ensure it is replaced wit...

Page 3: ...se this with the compressor displacement which is the air taken in by the compressor air in Air out is always less than air in due to losses within the compressor 5 1 STARTING STOPPING THE COMPRESSOR 5 1 1 To turn the compressor on use the switch on the top of the pressure switch housing figs 6 1 and 7 1 Turn the switch clockwise to position I to start the compressor and anti clockwise to position...

Page 4: ...tions to be carried out weekly a Drain condensation by opening the valve located under the tank fig 9 Place a container under the valve and open the valve by turning anti clockwise WARNING Take care if there is still pressure inside the cylinder as water could flow out with considerable force Recommended pressure 1 2bar max b Check oil level and if necessary top up 6 4 Operations to be carried out...

Page 5: ...ed Service Agent Compressor does not reach max pressure Filter clogged Head gasket or valve fault Replace filter element Contact Authorised Service Agent Compressor noisy with metallic knock Low oil level Bearing or piston damage Turn off and top up oil immediately Contact Authorised Service Agent fig 10 fig 11 Sealey Group Kempson Way Suffolk Business Park Bury St Edmunds Suffolk IP32 7AR 01284 7...

Reviews: