Summary of Contents for FT500 Series

Page 1: ...PROUDLY MADE IN THE USA C e rtified Compa n y ISO 9001 2008 FT500 Batch Flow Processor Instructions ...

Page 2: ......

Page 3: ... 4 Dimensions Page 4 Specifications Page 4 Installation Mounting Page 5 Connections Page 5 Settings and Operation FT520 Batch Controller Page 6 FT520 84 Filter Regeneration Page 7 FT520 86 Flowrate Alarm Page 8 FT522 Usage Monitor Page 9 Repair Troubleshooting Repair Page 10 Troubleshooting Page 10 Warranty Seametrics Limited Warranty Page 11 ...

Page 4: ...5 C Enclosure Precision cast aluminum NEMA 4X panel or wall mount configuration Batch Outputs Two form C SPDT relays 115 Vac 6 A max Max Pulse Output 100 mA at 60 Vac Vdc opto isolated open collector Memory Type Non volatile EEPROM with auto backup Sensor Power 12 Vdc 10 mA Display Totalizer 8 digit Rate 5 digit backlit Units Volume Gallons cubic feet cubic meters millions of gallons milliliters f...

Page 5: ...sed NC contacts Analog Connection if used This output can be configured 4 20 mA 0 5 V or 0 10 V by placing a jumper in the correct position on the analog header The analog switch next to the header selects active powered or passive unpowered output NOTE Consult factory to change internal firmware when changing switch position When using the 12 Vdc powered input you may only select passive output P...

Page 6: ...at the selected volume intervals if this feature is in use If a pulse output is not needed pulse out does not need to be set SET Pulse scaled Output 2 An output pulse is activated at the selected volume intervals if this feature is in use If a pulse output is not needed pulse out does not need to be set SET 20 mA Rate The SET 20 mA RATE programs the maximum flow rate at which the output is 20 mA f...

Page 7: ...rvals if this feature is in use If a pulse output is not needed pulse out does not need to be set SET Pulse scaled Output 2 An output pulse is activated at the selected volume intervals if this feature is in use If a pulse output is not needed pulse out does not need to be set SET 20 mA Rate The SET 20 mA RATE programs the maximum flow rate at which the output is 20 mA full scale at 5 V or 10 V SE...

Page 8: ... use If a pulse output is not needed pulse out does not need to be set SET Pulse scaled Output 2 An output pulse is activated at the selected volume intervals if this feature is in use If a pulse output is not needed pulse out does not need to be set SET 20 mA Rate The SET 20 mA RATE programs the maximum flow rate at which the output is 20 mA full scale at 5 V or 10 V SET Low Flow Alarm Set the de...

Page 9: ...rt in the flow sensor instructions based on pipe size SET Pulse scaled Output 1 An output pulse is activated at the selected volume intervals if this feature is in use If a pulse output is not needed pulse out does not need to be set SET Pulse scaled Output 2 An output pulse is activated at the selected volume intervals if this feature is in use If a pulse output is not needed pulse out does not n...

Page 10: ... Display reads normally flow rate incorrect Wrong K factor entered Check K factor enter proper one if in error Display reads normally no or wrong pulse output Wrong pulse output setting Check SetP to see if it is set correctly Polarity reversed on pulse output terminals Reverse leads and see if problem corrects Display reads normally no or wrong 4 20 mA output Wrong 20 mA setting Check Set20 to se...

Page 11: ...etrics which cause damage to the products or cause abnormally frequent service calls or service problems h A new warranty period shall not be established for repaired or replaced material products or supplied Such items shall remain under warranty only for the remainder of the warranty period on the original materials products or supplies i In the event that equipment is altered or repaired by the...

Page 12: ...Seametrics 19026 72nd Avenue South Kent Washington 98032 USA P 253 872 0284 F 253 872 0285 1 800 975 8153 seametrics com LT 65200029r1 1 20170503 5 3 2017 ...