B) AUT / S-S (Photocells Test):
The control unit is supplied by the manufacturer with photocell
Test programming enabled (in accordance with Standard EN
12453). If you wish to disable the function proceed as follows:
check that Extended Menu 1 is enabled (T. PAUSA and RIT.
ANTE LEDs flashing alternatively), with the SEL key positioned
on the flashing of AUT/ S-S LED then press the SET key, the
AUT/S-S LED will simultaneously stays on steadily and
programming is completed. Accordingly, the photocell test will
not be carried out, therefore even if not connected (if unused,
DS1 and DS2 inputs must be jumped), the control unit is
enabled for operation. Repeat the procedure to restore the
previous configuration.
Important
: In the
LRX 2299/NT – LRX 2212 NEW/NT
series
control panels the photocell test is deactivated by default, but
can be activated by following the procedure described above.
C) CODE ( Hydraulic Motors Maintenance Pressure ) :
The control unit is supplied by the manufacturer with the
hydraulic motors maintenance pressure function disabled. If you
wish to enable the function, proceed as follows: make sure that
you have enabled Extended Menu 1 (T. PAUSA LED and RIT.
ANTE LED start flashing alternately), with the SEL key position
on the flashing of CODE LED then press the SET key, the
CODE LED will simultaneously stay on steady and
programming is completed. Accordingly the control unit will
send a closing command every 2 hours to the motor for 2
seconds. Repeat the procedure to restore the previous
configuration.
D) INB. CMD. AP. LED ( Water Hammer ) :
The control unit is supplied by the manufacturer with Water
Hammer disabled. If you wish to enable the Water Hammer
function, proceed as follows: check that Extended Menu 1 is
enabled (RIT. ANTE LED and T. PAUSA LED start flashing
alternately), with the SEL key position on the flashing of
INB.CMD.AP LED then press the SET key, the INB.CMD.AP
LED will simultaneously switch on permanently and
programming is completed. If you wish to enable the Water
Hammer function to the power set through the "POWER"
Trimmer, repeat the operation described above, pressing the
SEL button twice instead of once (making the INB.CMD.AP.
LED flash rapidly). Repeat the operation to restore the initial
configuration.
Accordingly, we can facilitate the release of the gate and
therefore allow the proper execution of the opening phase. In
fact, the control unit, before starting the opening phase sends a
closing command for 2 seconds with power relative to the
choice selected.
E) T. MOT. ( Closing Hammer ) :
The control unit is supplied by the manufacturer with the
Closing Hammer Function disabled. If you wish to enable the
Closing Hammer function, proceed as follows: make sure that
you have enabled Extended Menu 1 (RIT. ANTE LED and T.
PAUSA LED start flashing alternately), with the SEL key
position on the flashing of T.MOT. LED then press the SET key,
the T.MOT. LED will simultaneously switch on permanently and
programming is completed. If you wish to enable the Closing
Hammer function to the power set through the "POWER"
Trimmer, repeat the operation described above, pressing the
SEL button twice instead of once (making the T.MOT. LED flash
rapidly). Repeat the operation to restore the initial configuration.
Accordingly the control unit, if functioning with Deceleration
during closing, will reach (after having completed the
deceleration closing phase) a time of 1 second with power
relative to the choice selected in order to overcome the gate
installed.
F) T. MOT. PED. LED ( 4x Limit switch / 4x Safety device ) :
The control unit is supplied by the manufacturer with the 4 x
Motor 1 and 2 inputs Limit switch enabled. If you wish to enable
the Safety Devices inputs function, proceed as follows: make
sure that you have enabled Extended Menu 1 (RIT. ANTE LED
and T. PAUSA LED start flashing alternately), by using the SEL
key select the flashing T. MOT. PED. LED and press the SET
button: T. MOT. PED. LED stays steadily lit and programming is
complete.
Repeat the operation to restore the initial configuration.
This way, the control unit changes operation of the 4 Limit
switch inputs in 4 Safety Devices inputs with the following
operation:
FC AP1 ( Safe opening ) :
If the device trips during closing, it is ignored. If it trips during
opening, it Stops + gate motion is reversed for 2 sec.
FC AP2 ( Safe opening ) :
If the device trips during closing, it is ignored. If it trips during
opening, it Stops + gate motion is reversed for 2 sec.
FC CH1 ( Safe closing ) :
If the device trips during opening and closing, it always Stops +
gate motion is reversed for 2 sec.
FC CH2 ( Safe opening and closing ) :
If the device trips during opening, it Stops + gate motion is
reversed for 2 sec. If it trips during closing, gate motion is
reversed.
Warning:
Jumper if some of these inputs used as Safety
Devices are not used.
EXTENDED MENU 2
The control unit is supplied by the manufacturer with only the
option of directly selecting the functions listed in the main menu.
To enable the functions listed in Extended Menu 2, proceed as
follows: open Extended Menu 1 (as instructed in the respective
section), then press and hold the SET key for 5 seconds, the T.
PAUSA LED and RIT. ANTE LED will flash simultaneously,
accordingly, you have 30 seconds to select the functions of
Extended Menu 2 using the SEL and SET buttons. After
another 30 seconds, the control unit returns to the main menu.
---------------------- EXTENDED MENU 2 -----------------
Reference LED LED Off LED On
A) 1-2 MOTORS
Follow Me = OFF Follow Me = ON
B) AUT / S-S PreFlash. and Cort. L=OFF PreFlash. or Cort. L. =ON
C) CODE Pause Lamp. = OFF Pause Lamp. = ON
D) INB.CMD.AP SOFT START = OFF SOFT START = ON
E) T. MOT. El. Gate CMD PED = OFF El. Gate CMD PED = ON
F) T.MOT.PED. PUL=PUL - PED=PED PUL=AP - PED=CH
G) T. PAUSA Flashing beacon ON/OFF simultaneous
H) RIT. ANTE Flashing beacon ON/OFF in simultaneous
A
) 1-2 MOTORS ( Follow Me ) :
It is possible to set the "Follow Me" function on the control unit:
this function can only be programmed if a Pause Time has
already been programmed, and it is used to shorten the Pause
time to 5 sec after the photocell connected to DS1 disengages,
i.e. the gate closes 5 seconds after the user has passed
through.
If you wish to enable the function, proceed as follows:
make sure that you have enabled Extended Menu 2 (T. PAUSA
LED and RIT. ANTE LED start flashing simultaneously), ANTE
CH Led), with the SEL key position on the flashing of
1-2
motors Led then press the SET key, the 1-2 MOTORS Led will
simultaneously switch on permanently and the programming is
completed. Repeat the procedure to restore the previous
configuration.