Document number: SG104148TEN
Revision: B01
Issue date: 20.8.2012
Copyright© 2012 Sécheron SA - This document is not contractual and contains information corresponding to the level of technology at the date of release.
File: e-UR46-8S_trouble_en.fm
E-49
UR46-81/82S
Trouble shooting
E.4
Replacement of the auxiliary contacts
To be performed in case of a damaged auxiliary contact (for example, by a short-circuit).
a) Disconnect the earth connection nut (7).
b) Remove the auxiliary contacts housing (1) and the transparent cover (2).
c) Remove the first switch (3), then the first insulation sheet (4) and continue until you find the
defective switch (by testing them with an electric multi-meter).
d) Mark and disconnect the 3 or 4 wires and replace the defective switch.
e) Connect the wires.
Note!
To wire the 5U type (3 wires - reversing contacts), remove the connection (6) from the old
switch (3) and refit it on the new switch.
f)
Replace the switches (3) and insulation sheets (4) in the reverse order to which they were
removed.
g) Slowly push the plate (8) by hand to check the function of the five switches (3) by the sound
of the switching noise.
h) Slide the cover (2) back on.
i)
Attach the auxiliary contacts housing (1) with screws tighten to a torque of 2 Nm.
j)
Tighten the earth connection nut (7) to a torque of 2 Nm.
03633
7
2
1
1
4
3
8
6
5
2
Summary of Contents for UR46-81S
Page 68: ...Secheron ...