background image

ENFORCER Access Power Distribution Boards 

SECO-LARM U.S.A., Inc. 

5

 

Installation (Continued): 

 

 

iii.

 

Connect the power supply's positive terminal to the power distribution board output 
terminal for this device marked "C." 

iv.

 

For fail-safe operation, connect the positive input of the powered device to the 
terminal marked "NC." 

v.

 

For fail-secure operation, connect the positive input of the powered device to the 
terminal marked "NO." 

c.

 

Unswitched auxiliary power outputs (to provide power to card readers, keypads, etc.) 

i.

 

Connect the positive input of the powered device to the terminal marked "C." 

ii.

 

Connect the negative input of the powered device to the terminal marked "COM." 

NOTE: 

Keep power limited wiring separated from non-power limited wiring (AC input, battery 

wiring) by a minimum distance of 

1

/

4

" (7mm) and use separate knockouts in the 

enclosure. 

5.

 

Connect each controlling device (card reader, keypad, RTE plate, etc.) to the corresponding 
input terminal for the particular device to be controlled. Inputs are activated by normally open 
or open collector sink inputs. 

a.

 

Normally open (N.O.) input triggers:  

i.

 

Connect the devices to the terminals marked "IN" and "GND" that correspond to the 
power output terminals of the device to be controlled.  

b.

 

Open collector sink inputs: 

i.

 

Connect the access control panel open collector output to the power distribution 
board's input terminal marked "IN." 

ii.

 

Connect the access control panel open collector's common (negative) to the power 
distribution board's input terminal marked "GND." 

6.

 

Connect an Auxiliary Interface Control Panel (AICP) to the power distribution board's Aux. 
Interface. A normally open, normally closed, or polarity reversal input from an AICP signaling 
circuit will trigger selected outputs. To enable AICP disconnect for any output, set the 
corresponding DIP switch for that output to "ON." To disable AICP disconnect for any output, 
set its corresponding DIP switch to "OFF" (default, "OFF"). 

a.

 

Normally open (N.O.) input: 

i.

 

For a non-latching hookup, refer to the instructions for Fig. 1 on pg. 7. 

ii.

 

For a latching hookup, refer to the instructions for Fig. 4 on pg. 7. 

b.

 

Normally closed (N.C.) input: 

i.

 

For a non-latching hookup, refer to the instructions for Fig. 2 on pg. 7. 

ii.

 

For a latching hookup, refer to the instructions for Fig. 5 on pg. 7. 

c.

 

AICP signaling circuit input trigger 

i.

 

For a polarity reversal input from the AICP Auxiliary Output, refer to the instructions 
for Fig. 3 on pg. 7.  

7.

 

The AICP Auxiliary Output may also be connected as a dry form C output as follows: 

a.

 

Connect the device to be triggered by the unit's dry contact output to the power distribution 
board's Aux. Interface terminals as follows: 

i.

 

For normally open output, connect to the terminals marked "NO" and "C." 

ii.

 

For normally closed output, connect to the terminals marked "NC" and "C." 

NOTE: 

The unit should be tested at least once a year for proper operation. Voltage on each output 

should be tested for both triggered and untriggered states and the operation of the AICP 
must be simulated.  

Summary of Contents for SLI ENFORCER PD-4PTQ

Page 1: ...d for emergency input Auxiliary supervision relay 1A 28VDC Equipped with dry and wet trigger inputs blade versions only Includes auxiliary interface to enable emergency egress alarm monitoring or to t...

Page 2: ...t DPDT 1A 28VDC LEDs Status 4 red on when relay is energized 8 red on when relay is energized Auxiliary Interface 1 green on when auxiliary input is triggered alarm condition Operating humidity 0 95 O...

Page 3: ...INTERFACE AUX OUTPUT AUX INTERFACE 10A 250V POWER CONTROL Terminal Group Terminal Labels Description of Use or Function Power 12 24 VAC VDC Power supply required Control Can be connected to a second...

Page 4: ...the board in a supply box making sure to use compatible spacers between the board and the metal back see pg 8 for ENFORCER Access Control Power Supply instructions 2 Connect the main power supply to...

Page 5: ...cess control panel open collector s common negative to the power distribution board s input terminal marked GND 6 Connect an Auxiliary Interface Control Panel AICP to the power distribution board s Au...

Page 6: ...utputs are connected to the In and the GND 2 Switched devices outputs 1 4 include both fail safe and fail secure examples 3 A keypad is connected both to control the electric strike but also to the C...

Page 7: ...a jumper between the T and INP terminals see Fig 2 3 For a polarity reversal input from the AICP output connect the and terminals from the AICP control circuit to the two terminals INP on the Aux Int...

Page 8: ...n is limited to the repair or replacement of any defective part if the unit is returned transportation prepaid to SECO LARM This Warranty is void if damage is caused by or attributed to acts of God ph...

Reviews: