background image

Z01   Door

 Belongs  to  partition

1

5

Each zone must be assigned to a partition. All zones are assigned to 

the 

1st partition by default.

Z01   Door

 Definition

Entry/Exit

6

Setting the zone definition is partly determined by the arming mode:
     

Entry/Exit

 - used for Entry/Exit doors. A zone must be closed during arming and when the delay expires. 

Entry delay will be available when

 the

 system is armed in 

Away

 or 

Stay

 mode. 

     

Interior - 

usually assigned to motion detectors and to interior doors. Violation of this zone will not trigger an 

alarm when 

the 

system is armed in 

Night

 or 

Stay

 mode.

     

Perimeter 

or

 Instant

 - usually intended for non-exit/entry doors, window protection, shock detection, and 

motion detectors. A zone goes immediately into an alarm state when violated while armed.
     

24h Burglary

 - a violation of such a zone causes an instant intrusion alarm, regardless of the system’s state.

     

24h Panic Silent 

- used for external panic buttons. If violated, an immediate panic alarm is triggered, with the 

exception that there is no audible indication of the violation.
     

24h Panic Audible

 - same as 

Panic Silent

,

 

except that the alarm will be audible.

     

24h Tamper - 

the tamper function is continuously operational. When a 

24h tamper

 zone is activated, a 

tamper alarm is generated.
     

24h Fire

 or 

24h Smoke -

 for smoke or other types of fire detectors. To avoid false alarms, zone attribute 

Fire 

Verification

 is recommended to use.

     

24h Fire button

 - for external auxiliary emergency alert buttons. If violated, an immediate fire alarm will 

sound, regardless of the system’s state.
     

24h Medical button - 

for external auxiliary emergency alert buttons. If violated, an immediate medical alarm 

will sound, regardless of the system’s state.
     

24h Fire supervisory

,

 24h Low Water Level

24h RF Jam

,

 24h Gas Detected

,

 24h Water leakage

,

 24h High 

Temperature, 24h Low Temperature - 

this group of definitions is used for 

the

 24h technical zones to report about 

abnormalities in the environment.

      Control

 - 

z

one is mostly used to arm/disarm the system (

Key-switch

 zone). Momentary and maintained key-

switch arming are available. This definition can also be used to turn On / Off the PGM output. Violation of this 
zone will not trigger an alarm, regardless of the system’s state.

      Follower  - 

usually assigned to motion detectors and to interior doors protecting the area between entry door 

and the keypad. This zone(s) causes an immediate intrusion alarm when violated unless an 

Entry/Exit

 zone was 

violated first. Violation of this zone will not trigger an alarm when the system is armed in 

Night

 or 

Stay

 mode.

      Follower Night Armed 

- this zone is the same as the 

Follower 

zone, but violation of this zone will not trigger 

an alarm when the system is armed in 

Stay

 mode.

      Interior Night Armed - 

this zone is the same as the 

Interior 

zone, but violation of this zone will not trigger an 

alarm when the system is armed

 in 

Stay

 mode.

      Entry/Exit Forced

 - same as 

Entry/Exit

 zone but unlike a regular entry/exit zone this zone can be violated 

before the arming. 

Short  programming manual - basic information 

Intruder alarm system

System with  

KM24, KM24A

, KM24G keypads

Z01   Door

 Supervisory window

2h

6

Specifies  how  often  the  system  checks  for  supervision  signals,  identifying  each  of  the  system’s  wireless 
detectors. The system generates a local trouble signal identifying the zone of any wireless detectors from which 
a signal is not received during the specified interval. Control panel then sends the supervision report code to the 
CMS. 

Note:

 

0 hours disables the supervision. If there are many detectors in the system, due to increased 

collision effect, it is recommended to set the supervision time to a minimum of 2 hours.

Z01   Door

 Zone  speed

0,4 sec

7

The loop speed menu enables you to set different times for which zone violation must exist before the zone will 
trigger an alarm condition. Normally zone speed is within 0,1 - 2,5 seconds  range. With 

Vibration

 zone loop type 

selected, the zone speed must be within 0,01 - 0,25 seconds range (fast zone). This zone loop speed time can 
be defined only for zones located on the control panel.

Z01   Door

 Entry  Delay

30 sec

8

Used for 

Entry/Exit 

or

 Entry/Exit Forced

 zones. Entry delay time is programmable within 1 - 255  seconds range.

Z01   Door

 Enable  Bypass

Yes

9

This attribute permits zone bypassing by authorized system users. If

 No

 is displayed as an option, then the zone 

cannot be manually bypassed.

Z01   Door

 No  alarm

No

9

Used for 

24h High temperature

 or 

24h Low temperature

. A zone with this attribute will not trigger an alarm, but 

can start PGM action.

Z01   Door

 Arm  on  exit

No

11

This attribute is only used for 

Entry/Exit

 or 

Entry/Exit Forced

. With this attribute being set - the system will finish 

an exit delay countdown and will arm the system immediately after the entrance door will close.

Z01   Door

 Exit  Route

No

11

With this attribute being set - a zone with 

Interior

 definition can be violated during an exit delay.

Z01   Door

 Entry  Route

No

10

With this attribute being set - a zone with 

Interior

 definition can be violated during an entry delay.

Z01   Door

 Fire  verification

No

10

This attribute is used in fire (smoke) verification procedure. Power to the smoke detector(s) in the affected zone 
will cut off and then restore. If a subsequent detection occurs in the same zone within a predefined time of the 
first detection, the system will emit a fire alarm. It’s recommended to use +PGM as fire detector power supply.

Z01   Door

 Limit alarms

Yes

13

Repeated violation of the same zone, often resulting in a false alarm and usually arising due to a malfunction, an 
environmental problem, or incorrect installation of a detector or sensor. By default, 

the

 system is set to make a 

Used for 

24h High temperature

 or 

24h Low temperature. 

Enter the temperature. Use

 [



]

 

or [

]

 to change 

temperature sign (+ or -). 

Note: 

temperature field will be visible if wireless detector is in use.

Z01   Door

 Temperature

+30 C

9

Page 6

Summary of Contents for BK4

Page 1: ... the tab Project data sending receiving 3 Once you customize the predefined template you can use it to program an individual system or thousands of systems 4 DO NOT FORGET to upload the customized template further project back to the keypad use the tab Project data sending receiving Fig 1 USB connection Upon power up of the system the keypad will display a phrase First Start Press ENT It means tha...

Page 2: ... the customized project back to the keypad use the tab Project data sending receiving MANUAL REGISTRATION OF MODULES Control panel PAS808M supports up to 7 modules and control panels PAS816 PAS832 P16 P32 P64 supports up to 15 modules If there are a few modules with incl enabled virtual modules EXT116VM on P series control panels the same default addresses in the system for example several EXM800 ...

Page 3: ...s are programmed in the system program system timers in menu Main menu Settings Timers M00 Control Panel 1 Name Control Panel It is recommended to give an appropriate name to the module The module name will appear on keypad s LCD if there will be any trouble with the module 2 M00 Control Panel Address 00 Registered module address is shown in a second row and on the upper left corner of LCD eg M00 ...

Page 4: ... MC and IR Anti Sabotage Roller Anti Sabotage No 5 6 M06 PROX8 Unknown tag No actio 13 The proximity reader has 3 options on what it must do when the unknown proximity tag is detected No action Indication module starts blinking red and starts emitting an annoying noise Indication and alarm module starts blinking red and starts emitting an annoying noise The alarm siren will be triggered after 3 at...

Page 5: ...e Roller special purpose zone loop type exluding PAS808M Wireless Z01 Door Address 00_1 A 2 Z01 Door Address 00_1 B 2 Page 5 Wireless detectors can be enrolled using serial number in a system with following firmware version or higher control panel P16 P32 P64 v 5 00 wireless zone expansion module EXT116S v 5 000 keypads KM24 KM24Aarba KM24G v 5 000 keypads KM25 v 5 000 software MASCAD v 1 9403 GSM...

Page 6: ...m is armed in Stay mode Entry Exit Forced same as Entry Exit zone but unlike a regular entry exit zone this zone can be violated before the arming Short programming manual basic information Intruder alarm system System with KM24 KM24A KM24G keypads Z01 Door Supervisory window 2h 6 Specifies how often the system checks for supervision signals identifying each of the system s wireless detectors The ...

Page 7: ...tput triggering source otherwise the PGM will not work correctly Not used unused PGM output should be programmed as Not Used FireAlarm output activates if an alarm occurs on the selected zone or module emergency keys Fire Burglary Alarm output activates if fire or burglary alarm occurs on the selected zone or module emergency keys Note output also activates when zone or module tamper conditions ar...

Page 8: ...eporting to CMS or to the user via the PSTN line PSTN Communicator Tel Number 1 8p45345464 2 Program the phone numbers as required Use the key to enter additional symbols p 3 sec pause P 10 sec pause w wait dial tone User must acknowledge the call by pressing the Ü key on the phone otherwise the control panel will call again Program the Account number This account number will be used for all repor...

Page 9: ...twork and another computer network frequently the public Internet A GSM GPRS module making a data connection must be configured with an APN to present to the network provider Contact your provider to verify the correct APN settings 4 GPRS settings Yes Send every 15 sec Periodic test The Periodic test menu enables you to set the time period that the module will automatically send a test report to t...

Page 10: ...in hours Period in hours Report time hh mm Report time hh mm x 1 1 x 01 00 xx 15 1 1 2 2 3 3 The programmed exit delay will be applied for all enabled partitions System Times Exit Delay 30 sec 1 Used for all partitions An audible Auto Arm Delay warning countdown will commence prior the automatic arming User that has right to stop auto arming can enter a valid PIN code at any time during the countd...

Page 11: ...stribution the wireless devices detectors PGM outputs and remote control can be programmed at factory to operate on different frequency Receiver can receive a signal from transmitter when operating frequency matches Wireless Subsystem 4 Attenuation 0 dB Due to the fact that there may be changes in the passive environment after installation it is possible to temporarily for 3dB attenuate the radio ...

Page 12: ... from the user U01 User 01 U01 User 01 Rights Arm Disarm Yes Clear alarm Yes Abort arming Yes All Rights Selected 7 7 All system users have all rights assigned by default However it is possible to change them The user has access to the following Arm Disarm Clear alarm Abort arming Bypass zones Edit settings View Event log Test fire zones Reporting test Run other tests Control PGM outputs Edit syst...

Page 13: ...GISTER KEYPAD KM24G PROGRAMMING WIZARD KM24G Service Mode Unregister Modules Service Mode Unregister keypad Service Mode Programming Wizard Used to unregister system modules The message First Start Press ENT will appear on keypad s LCD screen when this procedure will end Used to unregister the keypad from the system Step by step programming wizzard with explanations and wiring schemes 5 7 6 Servic...

Page 14: ...Use SERIALaccount Account number Protocol Transport Receiver No 2 Use as backup for Rec 1 Address Port Use SERIALaccount Account number Protocol Transport Periodic test Send every Obtain IPautomatic IPaddress Subnet mask Gateway Obtain DNS automatic DNS server 1 DNS server 2 Periodic Test Settings Period in hours Period in days Period time hh mm Name In Use Exit Delay No Entry Delay Arming timer P...

Reviews: