INSULATED CHASE CONSTRUCTION
Facing
1. Combustible wall (such as Gyproc) must be installed flush with the fireplace. It may
not project in front of and on the fireplace (i.e. the steel façade of the fireplace) (fig. 12)
2. Decorative frame made of combustible material cannot project in front of and on the
fireplace steel front, in the space delimited by the width of the unit (38") and a height of
48" from the base of the appliance.
3. Non-combustible materials such as brick, stone or ceramic tile may project in front of
and onto the fireplace facing (figure 13).
Mantel
The mantel must be installed at least 48" (1016 mm) above the base of the fireplace
(figure 12).