16
I
NSULATED
R
ADIATION
S
HIELD
(RSI)
In cold climate locations, an insulated firestop may be
installed at the ceiling level. This will minimize heat loss
around the chimney at this location.
The insulated radiation shield should be installed from
below and the attic radiation shield installed from above.
U
NIVERSAL
R
OOF
S
UPPORT
I
NSTALLATION
This support has three possible uses:
1.
For ASHT+ / and S-2100+ / , it must be used on a roof to support the chimney.
2.
It may be used on a floor, ceiling or roof above an offset to support the chimney above the offset.
3.
It may be used on a floor, ceiling or roof as a supplementary support when the chimney height exceeds 15 ft.
Table 7 gives maximum height of supported chimney.
Note: For the AC chimney, a support section must be used every 40' instead of the roof support.
FOR INSTALLATION INSTRUCTIONS REFER TO THE MANUAL PROVIDED WITH THE ROOF
SUPPORT.
U
NIVERSAL
O
FFSET
S
UPPORT
I
NSTALLATION
This support is used to support a chimney above an offset. When the chimney offset is used to traverse a wall, this
support may be used on the wall to support the chimney. The maximum height is given in Table 7.
MAXIMUM HEIGHT OF CHIMNEY SUPPORTED
CHIMNEY
UNIVERSAL OFFSET SUPPORT
UNIVERSAL ROOF SUPPORT
7" ASHT+ /
8" ASHT+ /
24
"
(7.30 m)
22
"
(6.70 m)
55
"
(16.75 m)
48
"
(14.63 m)
7" S-2100+ /
8" S-2100+ /
12
"
(3.65 m )
10
"
(3.10 m )
20
"
(6.10 m)
20
"
(6.10 m)
7" AC
8" AC
50
"
(15.20 m)
50
"
(15.20 m)
40
"
(12.19 m)
40
"
(12.19 m)
Table 7
FOR INSTALLATION INSTRUCTIONS, REFER TO THE MANUAL PROVIDED WITH THE OFFSFT
SUPPORT.
ASHT+ / S-2100+ - /
ATTIC
RADIATION
SHIELD
RSI
Figure 16