Secutron Inc.
21
Table 3 Battery Calculation Chart
Select a battery with an Amp-Hr. rating that is equal to or larger than the calculated minimum
Amp-Hr. battery required.
8
Select ‘standby’ time required (24 or 60 Hr.):
Hr.
9
Standby Amp-Hr. - multiply 8 × 7 = (Amps × Hr.):
Amp-Hr.
10
Select ‘alarm’ time required (0.08 or 0.5):
Hr.
11
Alarm Amp-Hr. - multiply 7 × 10 = (Amps × Hr.):
Amp-Hr.
12
Total Amp-Hr = standby Amp-Hr (9) + alarm Amp-Hr. (11):
Amp-Hr.
13
Multiply the total Amp-Hr. by the safety margin:
1.20
14
Total battery Amp-Hr required to support the system:
Amp-Hr.
Note:
The maximum battery allowed is 26 Ah. Install batteries outside the panel box. Total “Standby”
current is not to exceed 0.5 Amperes.