4.2.1 NAC Wiring Chart
Table 6 NAC Wiring Chart
Figure 13 Connecting Batteries
Maximum
Total Loop
(ohms)
Maximum
Current
(A)
18-Awg Wire
16-Awg Wire
14-Awg Wire
12-Awg Wire
ft
m
ft
m
ft
m
ft
m
8.00
0.25
615
188
978
297
1,538
469
2,500
762
5.00
0.50
308
94
488
149
769
235
1,250
381
2.70
0.75
205
63
325
99
513
156
833
254
2.00
1.00
154
47
244
74
385
117
625
191
1.60
1.25
123
38
195
59
308
94
500
152
1.30
1.50
103
31
163
50
256
78
417
127
Note:
This chart is based on a minimum source voltage of 22 volts and a maximum line loss of 2 volts
thus leaving a minimum of 20 volts at the last notification appliance.