Secutron Inc.
44
6.3.2 NAC Sounding Rate Programming
NAC1 and NAC2 can be configured to sound at either steady or temporal rate. The default
rate is steady.
Use the Zone 1 and Zone 2 Alarm, Supervisory and Trouble LED’s to program this function.
Press the Silence Alarm control to cycle through the programmable settings for each function.
Press the Silence Trouble control to cycle through the Zones. To proceed to the next
programming function cycle through the 2 zones.
The Trouble LED flashes when the panel is in programming mode.
The NAC1 Panel Status LED will illuminate steady.
Table 11 LED Indicators for NAC Sounding Rate Programming
Panel Status LED
Alarm, Supervisory and
Trouble LED’s
Programmable Setting Description
Steady (default)
The NAC will sound continuously.
Temporal
The NAC will sound the Temporal/ANSI Fire
Pattern: 0.5 seconds ON, 0.5 seconds OFF, 0.5
seconds ON, 0.5 seconds OFF, 0.5 seconds ON,
1.5 seconds OFF, repeat.
CPU
FAULT
Summary of Contents for MR-2605
Page 2: ......
Page 6: ...Secutron Inc vi...
Page 8: ...Secutron Inc viii...
Page 10: ...Secutron Inc x...
Page 70: ...Secutron Inc 70...
Page 71: ......