6.3.5 Waterflow Alarms Programming
Use the Zone 1 Alarm, Supervisory and Trouble LED’s to enable or disable the Waterflow
Delay Timer function.
Use the Zone 2 Alarm, Supervisory and Trouble LED’s to enable or silence the Silence
Waterflow Alarms function.
Press the Silence Alarm control to cycle through the programmable settings for each function.
Press the Silence Trouble control to cycle through the Zones. To proceed to the next
programming function cycle through the 2 zones.
The Trouble LED flashes when the panel is in programming mode.
The Ground Fault Status LED will illuminate steady.
Table 14 LED Indicators for Waterflow Alarms Programming
Panel Status LED
Alarm, Supervisory and
Trouble LED’s
Programmable Setting Description
Waterflow Delay Timer Disabled (default)
Alarms on Waterflow zones causes an immediate
alarm in the panel.
Waterflow Delay Timer Enabled
The panel starts a 60 second timer when the first
Waterflow zone enters alarm. The panel will not
restart the timer on subsequent Waterflow zone
alarms. When the timer expires, if any waterflow
zone is still in alarm, the panel will immediately go
into alarm. If any other type of fire zone enters
alarm during the waterflow delay countdown, the
panel immediately enters alarm.
Silence Waterflow Alarms Enabled (default)
Waterflow zones can be silenced without being
physically restored.
Silence Waterflow Alarms Disabled
Waterflow zones cannot be silenced until they are
physically restored. This applies to both automatic
signal silence, and the Silence Alarm button. If
there is a trouble on a Waterflow zone following
the alarm and alarm restore, the zone can be
silenced.
CPU
FAULT
Zone 1
Waterflow
Delay Timer
DISABLED
Zone 1
Waterflow
Delay Timer
ENABLED
Zone 2
Silence
Waterflow
Alarm
ENABLED
Zone 2
Silence
Waterflow
Alarm
DISABLED