background image

Smoke & Heat Detectors

Installation Instructions

General

These instructions apply to the MRI-2000 4” standard base and the MRI-2001 6” E-Z Fit 

base.

Installation

These products must be installed in accordance with the applicable NFPA standards, 

local codes and jurisdictional authorities. Failure to follow these instructions may result 

in failure of the detectors to report an alarm condition. Secutron is not responsible for 

detectors which are improperly installed, maintained and tested.

Before installing these products check the continuity, polarity and insulation resistance 

of all wiring. Check that siting is accordance with the   re system drawings and conforms 

to all applicable local codes such as NFPA 72.

Use 3" octagonal box for direct connection to the base. 4" octagonal and 4" square 

boxes may be used with proper UL listed mounting brackets. When mounting on a wall, 

install 4" to 12" from the ceiling. Use 3M Weatherban 606 Non-Flammable sealing com-

pound (or equivalent) to seal   eld wiring conduit opening in the electrical box, this will 

reduce the stack effect. Secure the base to the electrical box with appropriate screws. 

Do not overtighten the screws.

 The raised mark on the side of the base indicates the 

direction of the detector LED when   tted. Connect the shield, if required, to the SHIELD 

terminal on the base. For information on how to set the address of each device correctly 

refer to the section ‘Address Setting' overleaf.

39214-802/Issue 1

Technical Data

1

4

Detector model no

MRI-3300

MRI-3100

MRI-3200

Detector type

r

o

s

n

e

s

it

l

u

M

c

i

r

t

c

e

l

e

o

t

o

h

P

t

a

e

H

Working voltage

17–28V dc

17–28V dc

17–28V dc

Modulation voltage

V

9

5

V

9

5

V

9

5

Maximum alarm

current

3.4mA

3.4mA

3.5mA

Surge current

1.0mA

1.0mA

1.0mA

Supervisory current 

500

μ

A

400

μ

A

500

μ

A

Heat element rating

Mode 1 129°F (54°C)

Mode 5 212°F (100°C)

)

C

°

7

5

(

 

F

°

5

3

1

 

5

 

e

d

o

M

A

/

N

Control panel

SFC-500 Series

Test method

•Hair dr

yer

•Home safeguard

 Sensitivity test

•No Climb

•Gemini 501

•Home safeguard

 Sensitivity test

•No Climb

•Gemini 501

•Hair dr

yer (heat 

sensor only)

Installation

temperature

Minimum 32°F (0°C)

Maximum at least  

20°F (11°C) below 

rating

Minimum 32°F (0°C)

Maximum 100°F 

(38°C)

Mode 1-4

 Minimum 

32°F (0°C) 

Maximum 100°F 

(38°C)

Mode 5

 Minimum 

32°F Maximum at 

least 20°F (11°C) 

below rating

Compatibility Information

These smoke and heat detectors have been approved by Underwriters Laboratories Inc. 

For details of compatible control panels, please contact Secutron directly.

Secutron

25 Interchange Way, Vaughan, Ontario, Canada

Tel: (888) 732-8876, Fax: (905) 660-4113

LT-1027SEC

August 2013