-13-
12A4A2-00007E-8
5. Installation
5-1
Installing Condition
•
When mounting the EMG7 to panels, be sure to have enough room for inserting and removing SD cards,
cables, and mounting brackets.
•
Be sure that the ambient operation temperature (0
℃
to 55
℃
) and the ambient humidity (10%RH to 85%RH.
Wet-bulb temperature is 39
℃
or less) )are within their designated ranges.
•
“Ambient operation temperature” indicates both the display side and inside of cabinet where the EMG7 will be
installed.
・
EMG7 should be mounted perpendicular, but if it should be mounted in an angle, the angle shall not be more
than 30degrees from the vertical position shown in the illustration below:
・
When installing the EMG7 in a slanted panel of angle 30 degrees or more, please use forced air cooling to
ensure the temperature specification.
Inside cabinet
Display side
30°or less