6
|
COOLER LOCATION
Check proposed cooler location to ensure it is structurally
capable of supporting the weight of the cooler. If the roof is
structurally inadequate, provide an alternate load bearing
structure.
The ideal location for the cooler is in a central position on the
roof (away from sleeping areas and where people spend most
of their time) so that the duct runs are of approximately the
same length. Carefully consider neighbouring residences and
noise levels when locating the cooler, if necessary talk to the
customer and the neighbour before carrying out the installation.
Always locate the cooler where it will receive adequate fresh air
and not in a recess where it may be starved for air or where the
air is polluted.
Ensure location is a minimum of:
•
3m from a solid fuel heater flue,
•
1.5m from a gas flue,
• 5m from a sewer vent, and
• 600mm from a wall.
The cooler must be mounted at least 3m (preferably 5m) away
from any TV antenna or antenna cables. Make sure the cooler
is not between the antenna and the transmission tower that is
providing the television signal to the home.
Allow adequate access to and around the cooler for
maintenance. Provision must be made for access to electricity,
water supplies and drains.
Note!
Do you need to discuss the installation of items like
safety anchor points with the customer?
EXQ/EXS MODEL
X
ILL1204-C
ILL1385-B
EZQ MODEL