background image

    BREEZAIR TBQ/TBS OWNER’S MANUAL  

|  

7

 

ILL1897-A

SEASONAL MAINTENANCE - cont

HIGH DUTY CYCLE OPERATION 
MAINTENANCE

For coolers operating more than 12 hours 

per day continuously throughout the year the 

following maintenance program is required:

6 monthly maintenance:

 

•  Inspect the cooler and check the pump, 

drain valve (if fitted), solenoid and fan motor.  

•  Check the pads and replace as required. 

•  Check and clean the tank and the pump 

filter.

12 monthly maintenance: 

•  Replace plastic fan and motor collet and 

check motor shaft for wear.

Summary of Contents for Breezair TBQ

Page 1: ...OWNER S MANUAL TBQ TBS Evaporative Cooler English Original English Instructions ...

Page 2: ......

Page 3: ...up and operate this system This appliance can be used by children aged from 8 years and above and persons with reduced physical sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved Children shall not play with the appliance Cleaning and user maintenance...

Page 4: ... DRY 3 AUTOCLEAN 3 WATER MANAGEMENT 4 WATERMANAGER 4 DRAIN VALVE 4 CONTINUOUS BLEED SYSTEM 4 POWER OUTAGES 4 HEALTH REGULATIONS 4 MAINTENANCE 5 PRE SEASON 5 END OF SEASON 5 COOLERS WITH DRAIN VALVES 6 COOLER ISOLATION SWITCH 6 WATER DISTRIBUTION CHANNELS 6 REMOVING THE BLEED SYSTEM 6 HIGH DUTY CYCLE OPERATION MAINTENANCE 7 MAINTENANCE SCHEDULE SERVICE CHECKLIST 8 TROUBLESHOOTING 9 ...

Page 5: ...d the product to provide many years of economical trouble free cooling MAGIQTOUCH CONTROLLER SETTINGS MENU Your MagIQtouch Controller contains a settings menu which gives you access to information about your Breezair evaporative cooler and to extra functions including ABOUT APPLIANCE Access information about the appliances installed in your system MIN MAX SET TEMPERATURE You can change the minimum...

Page 6: ...vel reaches a preset level the WaterManager will open the drain valve and release saline water Fresh water will then be added diluting any minerals or salts accumulated The WaterManager will continue to monitor and drain water as required Alternatively the cooler can be set to drain saline water at a preset period of pump operating time This can be set by changing the salinity control method selec...

Page 7: ...e pad frames Ensure power is off at isolating switch inside the cooler Gently wash pad frames to remove any dust build up during winter IMPORTANT Do not damage the pads with high pressure water spray Inspect pad retention pins and washers for damage and that they are securely fitted Replace the bleed system if it was removed during previous maintenance and ensure the O ring is fitted If the cooler...

Page 8: ...towards you until the internal side clips disengage Pivot the pad frame outwards and lift up Take care not to damage the pad ILL1001 C REMOVING THE BLEED SYSTEM Unclip and remove the bleed system as shown SEASONAL MAINTENANCE cont REMOVING PAD FRAMES Insert a flat screw driver tip into the slot as shown and lever until disengagement occurs ...

Page 9: ...continuously throughout the year the following maintenance program is required 6 monthly maintenance Inspect the cooler and check the pump drain valve if fitted solenoid and fan motor Check the pads and replace as required Check and clean the tank and the pump filter 12 monthly maintenance Replace plastic fan and motor collet and check motor shaft for wear ...

Page 10: ...rvoir Pump Filter Water Probes System Washers Seals and O Rings replace as required Drain Valve Bleed System Operation Component Function Pump Operation Drain Valve Operation Motor Operation reset motor amps where required Solenoid Operation Wall Control Operation General Operation Water Level Set Point Water Fill Time Water Drain Time Water Distribution across Pads Airflow through system Outlets ...

Page 11: ...ooling Dry pads Ensure the water supply is turned on Then check the water flow to the pads Insufficient exhaust openings for conditioned air Ensure sufficient exhaust openings Excessive ambient humidity On days during the summer when the ambient humidity is high the cooler will not reduce the temperature as much as on drier days Cooler turns ON and OFF Fault in the cooler Contact the Dealer or Ser...

Page 12: ...ications are subject to change without notice Please consult with your dealer to confirm the specifications of the model selected MANUFACTURED BY SEELEY INTERNATIONAL PTY LTD 112 O SULLIVAN BEACH RD LONSDALE SA 5160 AUSTRALIA IMPORTED BY SEELEY INTERNATIONAL EUROPE LTD 5 PAPPLEWICK LANE HUCKNALL NOTTINGHAM NOTTINGHAMSHIRE NG15 7TN UNITED KINGDOM SEELEY INTERNATIONAL AMERICAS LTD 1202 NORTH 54TH AV...