INSTALLATION AND SET UP PROCEDURES. 

The equipment (motor + controller) is ready for operation ; connect the line 115VAC supply source with the earth connection (the 
section of additional line wires must be > 0,75mm²). 

 

DO NOT USE THE DRIVE SYSTEM IN AN EXPLOSIVE ATMOSPHERE

   

 DANGER : 

If changes on the calibrations are needed they must be done by qualified electrical maintenance personnel : 

THE 

TRIMMERS MUST BE ADJUSTED WITH INSULATED SCREW DRIVES

RXI CALIBRATION :- 

START THE MOTOR AND WAIT FEW MINUTES FOR THE THERMAL STABILIZATION 

  - MEASURE THE SPEED WITHOUT THE LOAD 

  

 

  - LOAD THE MOTOR AND CALIBRATE THE TRIMMER TILL THE SAME SPEED WILL BE OBTAINED

 

If changes on the internal wires connections or fuse exchange are needed  

TAKE-OFF THE MAIN SUPPLY BEFORE ANY 

OPERATION. 
AUTOMATIC RESTART OF THE CONTROLLER MAY OCCUR  IF THE LINE POWER IS TEMPORARY LOST. 

 CONNECTION OF EXTERNAL DEVICES :  PAY ATTENTION TO THE RIGHT CONNECTIONS OF THE INHIBIT AND  115VAC  

    

SUPPLY  

TROUBLESHOOTING. 

MOTOR  NOT RUN 

CHECK THE MAIN POWER CONNECTION 

ENSURE THE MAIN SWITCH TO “ON” 

ENSURE INHIBIT OPEN 

CURRENT LIMIT (CHECK THE CAUSE OF MOTOR OVERLOAD) 

BLOW FUSE  
(GREEN LED OFF)  

DAMAGE WIRES 

WRONG LINE VOLTAGE 

MOTOR SHORT CIRCUIT 

NO SPEED CONTROL 

CHECK THE POTENTIOMETER WIRES 

CHECK THE CONNECTOR TO EXTERNAL SPEED 

ALARM 
(RED LED ON) 

CHECK THE LOAD TO ENSURE THE RATED POWER OPERATION OF THE 
MOTOR AND IF THE ROTOR IS LOCKED  

 

5

Summary of Contents for 7S115C

Page 1: ...7S115C_USE_1 doc DATE 25 08 2003 REV 0 1 1 ...

Page 2: ...h acceleration of the motor to avoid shock for the load Current limited protection of the motor and max torque for the load known Thermal protection to ensure no overload long time operations Overload current protection to avoid damage to the drive system if the motor is stalled for few seconds Alarm LED indicator R x I compensation to ensure the constant speed operation in the whole range of load...

Page 3: ... Nm FREQUENCY PWM 18 KHz CONTROLLER MAX TEMPERATURE 80 C SPEED REFERENCE MANUAL 10K OHMS TEN TURNS POTENTIOMETER SPEED REFERENCE AUTOMATIC 4 20 mA EXTERNE SOURCE SPEED RANGE CONTROL 30 700 RPM TILL RATED TORQUE SERVICE AT RATED POWER S2 40 ADJUSTMENTS WITH TRIMMERS DESCRIPTION TRIMMER RANGE FACTORY SET MAX SPEED VMAX CW INCREASE 70V 600RPM 90V 780RPM 80V 680RPM ACCELERATION DELAY ACC CCW INCREASE ...

Page 4: ...ng ALARM LED indicates the thermal protection overload current alarm and power stage broken 4 20mA CONNECTOR optoinsulated input 4 20 mA pins 1 2 not insulated input inhibit pins 4 5 from external device for automatic operation RUN DRY CONNECTOR output supply 115 VAC pins 1 2 for external device inhibit pins 4 5 HI PRESS CONNECTOR output supply 115 VAC pins 1 2 for external device inhibit pins 4 5...

Page 5: ...HE TRIMMER TILL THE SAME SPEED WILL BE OBTAINED If changes on the internal wires connections or fuse exchange are needed TAKE OFF THE MAIN SUPPLY BEFORE ANY OPERATION AUTOMATIC RESTART OF THE CONTROLLER MAY OCCUR IF THE LINE POWER IS TEMPORARY LOST CONNECTION OF EXTERNAL DEVICES PAY ATTENTION TO THE RIGHT CONNECTIONS OF THE INHIBIT AND 115VAC SUPPLY TROUBLESHOOTING MOTOR NOT RUN CHECK THE MAIN POW...

Page 6: ...6 ...

Page 7: ...7 ...

Page 8: ...8 BRUSH CHANGE OPERATION ...

Reviews: