5.7 More Settings
5.7.1 Circuit breaker failure protection
The CB failure protection is based on supervision of phase currents during tripping events. Only af-
ter tripping this protective function becomes active. The test criterion is whether all phase currents
are dropped to < 2% x I
N
within t
CBFP
(Circuit Breaker Failure Protection). If not all of the phase cur-
rents have dropped to
< 2% x I
N
within this time t
CBF
(adjustable between 0.1
–2.0s), a CB failure is detected and the re-
lated relay is activated. The CB failure protection function is deactivated again as soon as the
phase currents have dropped to <2% x I
N
within t
CBFP
. The relay that is as-signed the failure protec-
tion function will drop after expiry of no more than 2.54 s.
The LEDs CB + t> will be flashing upon this parameterisation.
5.7.2 Adjustment of the slave address
By pressing push buttons <+> and <-> the slave ad-dress can be set in the range of 1-32.
The display shows RS1 to RS32
5.7.3 Setting of Baud-rate (applies for Modbus Protocol only)
Different transmission rates (Baud rate) from 2400 to 9600 Baud can be set for data transmission
via Modbus protocol. The rate can be changed by push buttons <+> and <-> and saved by press-
ing <ENTER>.
5.7.4 Setting of parity (applies for Modbus Protocol only)
The following three parity settings are possible:
„even“ = even
„odd“ = odd
„no“ = no parity check
The setting can be changed by push buttons <+> and <-> and saved by pressing <ENTER>.