Manual MRG3
SEG Electronics GmbH
DOK-TD-MRG3, Rev. D
57
5.10.5 Units of the measuring values
The measuring values can optionally be shown in the display as a multiple of the "sek" rated value
or as primary current. According to this the units of the display change as follows:
Phase current:
Indication as
Range
Unit
Secondary current
.000
– 40.0
x In
Primary current
.000
– 999.
k000
– k999
1k00
– 9k99
10k0
– 99k0
100k
– 999k
1M00
– 2M00
A
kA*
kA
kA
kA
MA
* for rated transformer current 2kA and up
Earth current
Indication as
Range
Unit
Secondary current
Active portion I
P
Reactive portionl I
Q
.000
– 15.0
±.00
– 15
±.00
– 15
x In
x In
x In
Primary earth
current
.000
– 999.
k000
– k999
1k00
– 9k99
10k0
– 99k0
100k
– 999k
1M00
– 2M00
A
kA*
kA
kA
kA
MA
Active portion I
P
±.00
– ±999
±k00
– ±k99
±1k0
– ±9k9
±10k
– ±99k
±M10
– ±M99
±1M0
– ±2M0
A
kA*
kA
kA
MA
MA
Reactive portion I
Q
±.00
– ±999
±k00
– ±k99
±1k0
– ±9k9
±10k
– ±99k
±M10
– ±M99
±1M0
– ±2M0
A
kA*
kA
kA
MA
MA
* for rated transformer current 2kA and up
Residual voltage
Indication as
Range
Unit
Secondary voltage
000V
– 999V
V
Primary voltage
.000
– 999 V
1K00
– 9K99
10K0
– 99K9
100K
– 999K
1M00
– 3M00
kV
kV
kV
kV
MV