7.8 Setting ranges and steps
7.8.1 System parameter
Setting range
Step
(range)
Tolerance
Y/D
Interlinking of the voltage
transformers
Y= star connection
D= delta connection
U_L1 L2 L3_prim
(sek) 0.05...500kV
Primary nominal trans-
former voltage
0.001
(0.05…0.20)
0.002
(0.20…0.50)
0.005
(0.50…1.00)
0.01
(1.00...2.00)
0.02
(2.00...5.00)
0.05
(5.00
…10.0)
0.1
(10.0...20.0)
0.2
(20.0…50.0)
0.5
(50.0...100)
1
(100...200)
2
(200…500)
U_L1 L2 L3
_sek
1V.. 400V
Secondary nominal
transformer voltage
1 (1...150)
2
(150...600)
Measured range 0
– 150V
Measured range 150
– 600V
Change-over via coding plugs
(see chapter 3.1.8)
UN_l1 L2 L3
(sek) 0.05...500kV
Primary nominal generator
voltage
0.001
(0.05…0.20)
0.002
(0.20…0.50)
0.005
(0.50…1.00)
0.01
(1.00...2.00)
0.02
(2.00...5.00)
0.05
(5.00…10.0)
0.1
(10.0...20.0)
0.2
(20.0…50.0)
0.5
(50.0...100)
1
(100...200)
2
(200…500)
I_L1 L2 L3_prim
(sek) 0.002... 50.0 kA
Primary nominal
transformer voltage
0.001 kA (0.002...0.200)
0.002 kA (0.200...0.500)
0.005 kA (0.500...1.00)
0.01 kA
(1.00...2.00)
0.02 kA
(2.00...5.00)
0.05 kA
(5.00...10.0)
0.1 kA
(10.0...20.0)
0.2 kA
(20.0...50.0)
IN_L1 L2 L3
(sek) 0.002... 50.0 kA
Primary nominal generator
current in phase
0.001 kA (0.002...0.200)
0.002 kA (0.200...0.500)
0.005 kA (0.500...1.00)
0.01 kA
(1.00...2.00)
0.02 kA
(2.00...5.00)
0.05 kA
(5.00...10.0)
0.1 kA
(10.0...20.0)
0.2 kA
(20.0...50.0)
U0_prim
(sek) 0.05...500kV
Primary nominal trans-
former voltage for residual
voltage
0.001
(0.05…0.20)
0.002
(0.20…0.50)
0.005
(0.50…1.00)
0.01
(1.00...2.00)
0.02
(2.00...5.00)
0.05
(5.00…10.0)
0.1
(10.0...20.0)
0.2
(20.0…50.0)
0.5
(50.0...100)
1
(100...200)
2
(200…500)