7.8.3 Time over current protection
Setting range
Step
(range)
Tolerance
I>
20...400 % (EXIT)
1
(20...50)
2
(50...100)
5
(100...200)
10
(200...400)
3% of the set value or
20mA
I_Char
Definite Time
DEFT
tI>
0.04 - 260 s (EXIT)
(definite time)
0.02
(0.04...1.0)
0.05
(1.0...2.0)
0.1
(2.0...5.0)
0.2
(5.0...10)
0.5
(10...20)
1.0
(20...50)
2.0
(50...100)
5.0
(100...200)
10.0
(200...300)
3% or
20 ms
I_Char
Normal Inverse
Type “A”
Very Inverse
Type “B”
Extremely Inverse
Type
“C”
RI - Inverse
Long Time Inverse
NINV
VINV
EINV
RINV
LINV
0.05 - 10 (EXIT)
(inverse time)
0.01
(0.05...0.5)
0.02
(0.5...1.0)
0.05
(1.0...2.0)
0.1
(2.0...5.0)
0.2
(5.0...10.0)
3% of the measuring value
of the current or
20ms (see
EN 60255-3)
tI>Reset
Reset Mode for tripping times
0 s; 60 s
I>>
20...400 % (EXIT)
1
(20...50)
2
(50...100)
5
(100...200)
10
(200...400)
3% of the set value or
10 mA
tI>>
0.04...10 s (EXIT)
0.02
(0.04...0.5)
0.05
(0.5...2.0)
0.1
(2.0...5.0)
0.2
(5.0...10.0)
0.5
(10…20)
1.0
(20…50)
2.0
(50…100)
5.0
(100…200)
10.0
(200…300)
3% or
20 ms
Table 7.3: Time over current protection