SEG Electronics GmbH
Manual MRG3
42
DOK-TD-MRG3, Rev. D
5.3.9 Parameter changeover switch/external triggering of the fault recorder
By means of the parameter-change-over switches it is possible to activate two different parameter
sets. Switching over of the parameter sets can either be done by means of software or via the ex-
ternal inputs RESET or blocking input. Alternatively, the external inputs can be used for Reset or
blocking of the triggering of the fault recorder.
Software-
parameter
Blocking input used as
RESET Input
used as
SET1
Blocking input
RESET Input
SET2
Blocking input
RESET Input
B_S2
Parameter changeover switch
RESET Input
R_S2
Blocking input
Parameter change over switch
B_FR
Ext. triggering of the FR
Reset input
R_FR
Blocking input
Ext. triggering of FR
S2_FR
Parameter change-over switch
Ext. triggering of FR
Table 5.2: Function of the digital inputs
With the setting B_S2 the blocking input (D8, E8) is used as parameter-set change-over switch.
With the setting R_S2 the reset input (D8, E8) is used as parameter-set change-over switch. With
the setting B_FR the fault recorder is activated immediately by using the blocking input. On the
front plate the LED FR will then light up for the duration of the recording. With the set-ting R_FR the
fault recorder is activated via the reset input. With the setting S2_FR parameter set 2 can be acti-
vated via the blocking input and/or the fault recorder via the reset input.
The relevant function is then activated by applying the auxiliary voltage to one of the external in-
puts.
Important note:
When functioning as parameter change over facility or used for external tripping, the external input
RESET is not available for resetting. If, for example, the external blocking input is used as parame-
ter set change-over switch, the protection functions must be separately blocked by the software (re-
fer to chapter 5.7.1).