SEG Electronics GmbH
Manual MRG3
56
DOK-TD-MRG3, Rev. D
As to operation:
After each reset (refer to 5.10.9) the min./max. storages are cleared. As from this instant there is no
time limit for the min./max. storage until the next reset By repeatedly pressing the
<SELECT/RESET> push button, the measuring values of the min./max. storage can be queried.
5.10.3 Unit of the measuring values displayed
The measuring values can optionally be shown in the display as a multiple of the "sek" rated volt-
age (xUn) or as primary rated voltage. According to this the units of the display change as follows:
Indication as
Range
Unit
Secondary voltage
000V - 999V
V
Primary voltage
.00V
– 999V
1k00
– 9k99
10k0
– 99k0
100k
– 999k
1M00
–- 3M00
V
kV
kV
kV
MV
Table 5.6: Units of the display
5.10.4 Indication of values measured for over current - and earth fault
protection
During normal operation, the following measuring values for over current
– and earth fault protec-
tion can be displayed.
Applies to MRG3-I, MRG3-IU0; MRG3-IE, MRG3-IER
Current in phase L1
LED: I + L1
Current in phase L2
LED: I + L2
Current in phase L3
LED: I + L3
Applies to MRG3-IU0; MRG3-U0; MRG3-IER
Residual voltage
LED: U + E
Applies to MRG3-IE; MRG3-IER
Earth current
LED: E
Applies to MRG3-IER
Active portion of the earth current
LED: E + EP
Reactive portion of the earth current
LED: E + E
Q
Angle between I
E
and U
E
LED: U + I + E