16
TB MRD1-G 11.97 E
4.6.5
Output relay settings
Reset time of the output relays:
With the exception of the self-supvervision relay, all exis-
ting output relays are assigned to the differential current
element. It is possible to define a proper reset time for
each individual relay. For this period - from the moment
of tripping - the relay remains in trip condition even if the
cause for the tripping does no more exist.
!
Note:
If the time for which the relay has been energized ex-
ceeds the adjusted reset time, the relay will release ins-
tantaneously after trip condition is canceld. This is parti-
cularly important for relay tests (test of the reset time)
where the test current is not switched off immediately
with tripping.
TRIP condition
Auslösebedingung
Relay energized
Relais angezogen
RESET TIME
Mindestkommandozeit
t
RESET TIME
Mindestkommandozeit
1
0
1
0
Fig.: Reset time
If a relay is to remain self-holding after tripping, the reset
time has to be set to „exit“. Setting as per customer’s re-
quirements can be noted down in the „selection“ line.
Relay
Basic equipment
Option
1
2
3
4
5
6
7
8
9
10
Function
I
diff
I
diff
>>
I
diff
I
diff
>>
I
diff
I
diff
>>
I
diff
I
diff
>>
ST
I
diff
I
diff
>>
I
diff
I
diff
>>
I
diff
I
diff
>>
I
diff
I
diff
>>
I
diff
I
diff
>>
Pre-adjustment
(in s)
0,20
0,20
0,20
0,20
•
0,20
0,20
0,20
0,20
0,20
Custom setting
•
Setting range: 0 -...1,00 s or exit (=latching- contact un-
til a DEVICE RESET is performed)