TB MRD1-G 11.01 E
33
Key
D
isplay
Parameters of the characteristic
Select
Setting range
(
•
no selection)
Pre-
adjust-
ment
actual
Set 1
S
et 2
S
et 3
S
et 4
Headline
none
•
••••
•
differential current Idiff at stabilizing current
Is/In=0 (see picture)
#
0.05...1.0
×
In
"
0.2
corresponding to Is/In=2
#
0.2...2
×
In
"
0.4
corresponding to Is/In=10
#
2.0...8.0
×
In
2.0
maximum permitted differential current
2.0...20.0
×
In
4.0
Offset of characteristic curve from static basic
characteristic curve
0.0...8.0
2.0
Table: Adjustable protection parameter
"
To get no negative slope in the characteristic part I the setting Idiff (Is=2) must not be less then the setting Idiff (Is=0).
The
MRD1
will check the inputs on this must.
#
In = Generator nominal current (or motor nominal current)