TB MRD1-G 11.01 E
55
Function- and signal inputs
Digital inputs
Thermal withstand capability
max. 310 V DC, 265 V AC
Coupling
galvanically isolated with common return wire
High-level
U > 18 V DC/AC
Low-level
U < 12 V DC/AC
Reset and blocking input
Thermal withstand capability
max. 310 V DC, 265 V AC
Coupling
galvanically isolated with common return wire (D8)
High-level
U > 18 V DC/AC function activated
Low-level
U < 12 V DC/AC Function not activated
Communication serial interface RS232C
Data transmission rate
9600 Baud
Connection
9-pin D-sub plug
Insulation voltages
DIN 19244 part 3 (IEC 870-3):
RS485
Data transmission rate
9600 Baud
Connection
plugged terminals
(RXT/TXD-P, RXT/TXD-N, Signal Ground, PE)
Insulation voltages
DIN 19244 part 3 (IEC 870-3):
Output relay
Contact class
IIB DIN VDE 435 part 120
max. breaking voltage:
250 VAC / 300 VDC
max. closing power:
1500 VA (250 V)
max. breaking power:
11 VA (220 VDC) at L/R = 40 ms
max. rating making current:
6 A
Short circuit current:
20A / 16 ms
Rated inrush current load:
64A
Returning time:
20 ms (without minimum operating time!)
Contact material:
AgCdO
Contact life span:
electrical:
2x10
5
switching points at 220V AC / 6A
mechanical: 30x10
6
switching points
Rated insulation voltage:
600 VAC (450V DC / 380 VAC)
(VDE 435, T303)
Air- and creeping distance VDE 0160
Insulation coordination:
pollution degree 3 for terminals,
pollution degree 2 for the electronic