22
TB XRN2 02.00 E
6
Special settings
6.1
Adjustable parameters
The following parameters can be set by the user him-
self:
XRN2-1 and XRN2-2:
∆
/Y
-
changing of input transformer connection
U<
-
threshold for undervoltage
t
U
<
-
tripping delay for undervoltage
U<<
-
threshold for undervoltage
t
U
<<
-
tripping delay for undervoltage
U>
-
threshold for overvoltage
t
U
>
-
tripping delay for overvoltage
U>>
-
threshold for overvoltage
t
U
>>
-
tripping delay for overvoltage
f
N
-
rated frequency
T
-
frequency measuring repetition in periods
f
1
-
threshold for frequency element 1
t
f1
-
tripping delay for frequency element 1
f
2
-
threshold for frequency element 2
t
f2
-
tripping delay for frequency element 2
f
3
-
threshold for frequency element 3
t
f3
-
tripping delay for frequency element 3
U
B
<
-
voltage theshold value for frequency and
vector surge measuring (or df/dt)
RS
-
Slave address of the serial interface
XRN2-2
only:
df
-
threshold for rate of frequency (df/dt) in
Hz/s
dt
-
measuring repetition for df/dt in periods
XRN2-1
only:
1/3
-
Vector surge tripping 1-of-3/3-of-3
∆Θ
-
Pickup value for vector surge in degree
6.2
Setting procedure
In this paragraph the settings for all relay parameters
are described in detail. For parameter setting a pass-
word has to be entered first (please refer to 5.4).
6.2.1
Parameter setting of over- and
undervoltage supervision
The setting procedure is guided by two coloured LEDs.
During setting of the voltage thresholds the LEDs U<,
U<<, U> and U>> are light green. During setting of
the trip delays t
U>
, t
U>>
, t
U<
and t
U<<
the according LEDs
light up red.
Thresholds of the voltage supervision
During setting of the threshold U>, U>>, U< and U<<
the displays shows the value directly in volt. The thresh-
olds can be changed by the <+> <-> push buttons and
stored with <ENTER>.
The undervoltage supervision (U< and U<<) as well as
the overvoltage supervision (U> and U>>) can be de-
activated by setting the threshold to "EXIT".
Tripping delay of voltage supervision
During setting of the tripping delays t
U<
, t
U<<
, t
U>
and t
U>>
the display shows the value directly in seconds. The
tripping delay is changed via the push button <+> and
<-> in the range of 0,04 s to 50 s and can be stored
with the push button <ENTER>.
When setting the tripping delay to "EXIT" the value is in-
finit meaning only warning, no tripping.