34
TB XRN2 02.00 E
8.4
Output relays
Relay type
Trip relays / change-over contacts
Alarm relays / change-over contacts
XRN2
1/2
1/2
3/1
Table 7.2: Output relays
The output relays have with the following characteristics:
maximum breaking capacity
250 V AC / 1500 VA / continuous current 6 A
for DC voltage:
ohmic
L/R = 40 ms
L/R = 70 ms
300 V DC
0.3 A / 90 W
0.2 A / 63 W
0.18 A / 54 W
250 V DC
0.4 A / 100 W
0.3 A / 70 W
0.15 A / 40 W
110 V DC
0.5 A / 55 W
0.4 A / 40 W
0.2 A / 22 W
60 V DC
0.7 A / 42 W
0.5 A / 30 W
0.3 A / 17 W
24 V DC
6 A / 144 W
4.2 A / 100 W 2.5 A / 60 W
Max. rated making current:
64 A (VDE 0435/0972 and IEC 65/VDE 0860/8.86)
Making current:
max 20 A (16 ms)
mechanical life span:
30 x 10
6
operating cycles
electrical life span:
2 x 10
5
operating cycles at 220 V AC / 6 A
Contact material:
silver cadmium oxide (AgCdO)
8.5
Power supply
Auxiliary voltage
16 - 360 V DC / 16 - 270 V AC
Power consumption:
standby 3 W operating 5 W
The connection terminals are C9, E9.
Max. allowed interruption of the
auxiliarxy supply without effecting
the function of the device:
50 ms
Propper connection of the earthing terminal
⊥
is essential for the EMC withstand of the relay.
Use wires of min. 1.5 mm
2
.
8.6
Inputs, blockage and reset
Low-range:
For rated voltages
24 V, 48 V, 60 V
U
AN
≥
10 V
U
AB
≤
8 V
Current consumption
1 mA DC bei 24 V
High-range:
For rated voltages
100 V, 110 V, 125 V, 220 V, 230 V
U
AN
≥
70 V
U
AB
≤
60 V
Current consumption
1.5 mA DC 270 V or 11.0 mA AC