8
8.
If you have a specific question not addressed in this manual, please call
301-694-
9601
, for technical support.
SYSTEM SHUTDOWN
1.
The SEI 1800/48-2U-P-ACC DC-UPS is an uninterruptible power system.
Therefore, removing the AC power feed to the unit will not shutdown the DC power
distributed to the loads until the battery pack is full discharged.
2.
Disconnect the AC power feed.
3.
Verify that the Battery Status LED and the System Status LED are flashing red.
4.
Press and hold the Manual Battery Test Switch for 5 seconds. The Battery Test
Status LED will quick flash red.
5.
All front panel LEDS will turn off, the unit fans will stop and the connected
equipment will power down.
THEORY OF OPERATION
Theory of Operation
The following will provide you with an outline of operations and a list of modules found in
the DC-UPS.
Modules
Rectifiers
System Controller/LVD
Battery Module
Distribution and Connectors
Alarm Contact Closures
Functional Block Diagram DC-UPS
RECTIFIERS
SYSTEM
CONTROLLER
DISTRIBUTION
MODULE(S)
BATTERY
PACK
ACC