background image

Version No. 1-2 - 04.06.2021

Doc. No. 9942691001

14 / 17

13. Trouble Shooting

Failure

Reason

Troubleshooting

 Unit

doesn't

start

 No power supply

 Check the electrical connection

 Cabinet temperature is lower
 than set point

 Wait until the set point is reached. The unit will  then
 start automatically. If the set point of the cabinet
 temperature  is too high, reduce it accordingly.

 Door contact is open

 Close the cabinet door or bridge the door contact.

Unit

doesn't

cool

 Compressor is faulty

 Please get in contact with one of our service
 partners.

 The circuit breaker of the
 compressor got activated

 Check the cooling capacity. In case the
 cooling capacity is too small, install the unit
 at a different place or add another cooling unit. 

 The evaporator and / or
 condenser are extremely dirty.

 Evaporator and /or condenser need cleaning

Evaporator

is iced up

 Not enough refrigerant due to
 leaking cooling circuit

 Refill refrigerant and re-seal cooling circuit.
 Please contact the manufacturer.

 Ambient temperature is much
 lower than the stated operating
 temperature range

 Install the unit at a different place. The ambient
 temperature must be within the stated operating
 temperature range.

 The control cabinet is
 not sealed properly.

 The control cabinet needs re-sealing.

 Fan or fan capacitor on
 the cold side are faulty

 Replace fan and/or fan capacitor.

Too much

condensate 

 Cabinet door not closed

 Ensure that cabinet door is closed properly

 The cabinet is not
 sealed properly

 The control cabinet needs re-sealing.

 Incomplete gasket between
 cooling unit and cabinet 

 Please check gasket

Uneven air circulation

inside the cabinet

 Cabinet air intake and air
 outlet are blocked 

 Ensure that both are unblocked and that air
 can circulate

 Cabinet volume too big for
 this cooling unit

 Check the cooling capacity. In case the cooling
 capacity is too small, install the unit at a different
 place or add another cooling unit. 

Condenser fan

doesn't work

 Fan is faulty

 Replace fan

Evaporator fan

doesn't work

 Fan is faulty

 Replace fan

Note: Before you contact one of our service partners please press the test button of the controller. Like this the
fans and the evaporator are getting switched on independent of the internal cabinet temperature. In cases of
emergency you can contact us under one of the tel. numbers stated on the last page.

Summary of Contents for 42691001

Page 1: ...3 4 Settings 4 5 Functional Principle 4 6 Technical Data 5 7 Mounting 6 8 Condensate management 8 9 Mounting Principle 9 10 Electrical Connection 10 11 Wiring Diagram 12 12 Taking into Operation 13 13...

Page 2: ...ons in the instruction manual must be adhered to General danger Indicates compulsory safety regulations which are not covered by a speci c pictogram such as one of the following High electric voltage...

Page 3: ...d with regards to Safety instructions Instructions on taking the cabinet out of operation Instructions on the prevention of unauthorised cabinet reconnection The electric equipment meets the valid saf...

Page 4: ...vironmental ratings please refer to the type plate data 5 Functional Principle The cooling unit for enclosures works on the basis of a refrigeration circuit consisting of four main components compress...

Page 5: ...low Volume System Unimpeded Ambient air circuit 250 650 m h Cabinet air circuit 125 250 m h Mounting Wall mounted Recessed Housing Material Mild steel powder coated Dimension A x B x C D E 600 x 320 x...

Page 6: ...irit level that the cabinet is in a horizontal position The max deviation from the vertical or horizontal is 3 degrees Air apertures To provide adequate air circulation and avoid temperature layers fr...

Page 7: ...the surface of the cabinet and remove the mounting template Stick the self adhesive unit seals on the outer surface of the cabinet for externally mounting and on the inner surface of the cabinet for...

Page 8: ...The condensation drain pipe should be attached as required e g in conditions of high humidity To install an oel cleaning drain 2 pipe please follow below steps Remove the plastic stopper from in the b...

Page 9: ...4 06 2021 Doc No 9942691001 9 17 9 Mounting Principle Do not use within the rst 15 minutes after installation 1 Mounting gasket 2 Mounting clip 3 M6 slotted set screw 4 Washer 5 Lock nut Fig 1 Recesse...

Page 10: ...external components it must be ensured that the wiring and connections are double insulated and safe against touch and protected from unauthorized and or accidental external contact Ensure that the co...

Page 11: ...minals T1 T2 Connect the door contact switch to terminals T1 T2 The contact must be closed when the cabinet door is closed SCCR Refer to UL508A Supplement SB and Seifert Systems document Short Circuit...

Page 12: ...Version No 1 2 04 06 2021 Doc No 9942691001 12 17 11 Wiring Diagram...

Page 13: ...on the PC board slightly to the right higher or to the left lower Close the unit in the prescribed manner Check that the new adjusted values meet the necessary requirements If necessary repeat the pr...

Page 14: ...Install the unit at a di erent place The ambient temperature must be within the stated operating temperature range The control cabinet is not sealed properly The control cabinet needs re sealing Fan o...

Page 15: ...ction The connections 1 2 and 3 4 are not low voltage 50V Regularly check the condenser pro le for dirt tests approx every 2 000 hours depending on the grade of ambient pollution Should the condenser...

Page 16: ...fan xing screws Connect the fan cable to the PC board and replace the board if necessary Dispose the old fan according to the environmental laws and regulations 16 Transport Storage Malfunction due t...

Page 17: ...rt Systems Ltd Seifert Systems Inc Seifert Systems Pty Ltd Albert Einstein Str 3 HF09 10 Wilerstrasse 16 B rnthal 1 Rep O ce 75 Circuit Drive 105 Lewis Road Hal Far Industrial Estate North Kingstown W...

Reviews: