Version No. 1-8 - 04.06.2022
Doc. No. 9943042001
14 / 19
13. Electrical Connection
Door Switch
The unit can be switched on and of via a door contact switch. When delivered the door contact terminals are
bridged on the female connector. To connect the door contact switch remove the bridge and connect door
contact switch. The contact must be closed when the cabinet door is closed.
Alarm Contacts
Alarm contacts rated according to:
EN60730-1
8(4)A N.O., 6(4)A N.C., 2(2)A N.O./ N.C. @ 250Vac
100000 cycles
UL 873
8A resistive 2FLA 12LRA, pilot duty C300 @ 250Vac
30000 cycles
These contacts are not suitable for fluorescent loads (neon lights, etc.) that use starters (ballasts)
with phase shifting capacitors. Fluorescent lamps with electronic controllers or without phase shifting
capacitors can be used, depending on the operating limits specified for each type of relay.
SCCR
Refer to UL508A Supplement SB and Seifert Systems’ document
Short Circuit Current Rating (SCCR)
on methods
how to modify the available short circuit current within a circuit in the panel.
Summary of Contents for 43042001
Page 8: ...Version No 1 8 04 06 2022 Doc No 9943042001 8 19 7 Performance graph...
Page 12: ...Version No 1 8 04 06 2022 Doc No 9943042001 12 19 11 Cut Out Dimension...
Page 13: ...Version No 1 8 04 06 2022 Doc No 9943042001 13 19 12 Dimension H x W x D...
Page 16: ...Version No 1 8 04 06 2022 Doc No 9943042001 16 19 15 Wiring Diagram...