5. Functional principle

The cooling unit for enclosures works on the basis of a refrigeration circuit consisting of four main
components: compressor (1), evaporator (2), condenser (3) and expansion device (4). 
The circuit is hermetically sealed and R134a refrigerant circulates inside it (R134a is chlorine free and has an
Ozone Destruction Potential [ODP] of 0 and a Global Warming Potential [GWP] of 1430). The compressor
compresses the refrigerant (thus taking it to high pressure and high temperature), and pushes it through the
condenser, where it is cooled by ambient air thus passing from the gas to the liquid state. At the liquid state it
then passes through the capillary pipe being a much lower pressure the refrigerant arrived to the evaporator
where it absorbs the necessary heat to change from liquid to gas state. The gas is then drawn back into the
compressor completing the cycle.

Condensation management
In environments with humidity and low internal enclosure temperatures, condensation may form on the
evaporator coil. Standard cooling units 43XXX0XXX  have a drain socket towards the bottom of the unit for
connection of the drain pipe. 
Cooling units 43XXX1XX include an internal condensate evaporator based on self-regulating PTC cartridges.
Condensate is drained to an internal recipient where it evaporates when in contact with the cartridge surface.
Resulting steam is directed towards the condenser. The PTC heater cartridge is permanently connected. The
recipient has an overflow socket at the bottom of the unit, for which a drain pipe is supplied.

Summary of Contents for 43042001

Page 1: ...6 6 Technical data 7 7 Performance graph 8 8 Mounting 9 9 Condensate management 10 10 Mounting Principle 11 11 Cut Out Dimension 12 12 Dimension H x W x D 13 13 Electrical Connection 14 14 Controller...

Page 2: ...issipation of heat from control cabinets and enclosures stationary not moving in order to protect temperature sensitive components in an industrial environment To meet the conditions of use all the in...

Page 3: ...nits based on the information diagrams or descriptions contained in this manual No liability can be accepted for damage and production caused by Disregarding the instruction manual Operating error Ina...

Page 4: ...regulations One can nd dangerous voltages above 50 V AC or above 100 V DC Behind the control cabinet doors On the power supply in the unit housing The unit has to be operated according to the type pl...

Page 5: ...air does not come into contact with the ambient air which may well be dirty or polluted Enclosure cooling units can dissipate large quantities of heat from sealed enclosures such as electrical enclos...

Page 6: ...e capillary pipe being a much lower pressure the refrigerant arrived to the evaporator where it absorbs the necessary heat to change from liquid to gas state The gas is then drawn back into the compre...

Page 7: ...ystem unimpeded Ambient air circuit 90 250 m h Cabinet air circuit 115 136 m h Mounting External Housing Material Mild steel powder coated Dimensions A x B x C D E 501 6 x 280 x 200 mm Weight 26 kg Cu...

Page 8: ...Version No 1 8 04 06 2022 Doc No 9943042001 8 19 7 Performance graph...

Page 9: ...e case a barrier or duct shall be provided to redirect the air ow Cooling unit enclosure air suction hole must be installed in the highest possible point When installing the unit on a door ensure it c...

Page 10: ...pipe should be attached as required e g in conditions of high humidity To install a drain pipe please follow below steps Remove the plastic stopper from in the base of the unit factory setting is lock...

Page 11: ...No 1 8 04 06 2022 Doc No 9943042001 11 19 10 Mounting Principle Do not use within the rst 15 minutes after installation 1 M6 screws 2 M6 at washers 3 M6 toothed washers 4 Cabinet 5 Sealing tape 6 Cool...

Page 12: ...Version No 1 8 04 06 2022 Doc No 9943042001 12 19 11 Cut Out Dimension...

Page 13: ...Version No 1 8 04 06 2022 Doc No 9943042001 13 19 12 Dimension H x W x D...

Page 14: ...ng to EN60730 1 8 4 A N O 6 4 A N C 2 2 A N O N C 250Vac 100000 cycles UL 873 8A resistive 2FLA 12LRA pilot duty C300 250Vac 30000 cycles These contacts are not suitable for uorescent loads neon light...

Page 15: ...ress Set to save the new setting To change the heating set point St2 units with internal heater only 1 Press Set till St1 appears on the display and release the button 2 Press again Set till St2 appea...

Page 16: ...Version No 1 8 04 06 2022 Doc No 9943042001 16 19 15 Wiring Diagram...

Page 17: ...power supply connector is incorrect Change phases inside power supply connector Unit doesn t cool External and internal fan work compressor does not work Compressor motor electrical failure Have comp...

Page 18: ...ions which meet the following conditions temperature range 40 C to 70 C Relative humidity at 25 C max 95 Returning the unit To avoid transport damage the unit should be returned in the original packin...

Page 19: ...G Seifert Systems GmbH Seifert Systems Ltd Seifert Systems Inc Seifert Systems Pty Ltd Albert Einstein Str 3 HF09 10 Wilerstrasse 16 B rnthal 1 Rep O ce 75 Circuit Drive 105 Lewis Road Hal Far Industr...

Reviews:

Related manuals for 43042001