background image

Version Nr. 1-8 - 21.06.2022

Doc. No. 9943152081

17 / 17

19. Parts supplied / Spare parts / Accessories

Description

QTY

Image

 

 

 

Instruction manual

1

 

CE Declaration

1

 

Mounting template

1

 

M6 * 16 bolts

8

A6.4 washer

8

M6 toothed washers

8

Lifting hook M8 x 12

1

PVC washer

1

Drain pipe

1

Female connector

1

Foam tape

 

Accessories:

Description

Order no.

 

 

Fibre filter media EU2

SP-43150001-O-1

Washable aluminium filter 

SP-43150001-BF-1

Stainless steel filter holder incl. filter media

SP-43150001-BG-1

Door contact switch

3100001

 

Seifert Systems GmbH

Seifert Systems Ltd.

Seifert Systems AG

Seifert Systems GmbH

Seifert Systems Ltd.

Seifert Systems Inc.

Seifert Systems Pty Ltd.

Albert-Einstein-Str. 3

HF09/10 

Wilerstrasse 16

Bärnthal 1

Rep. Office

75 Circuit Drive

105 Lewis Road

 

Hal-Far Industrial Estate

 

 

 

North Kingstown

Wantirna South

42477 Radevormwald

Birzebbuga, BBG 3000

4563 Gerlafingen

4901 Ottnang

26100 Cremona

RI 02852

3152 Victoria

Germany

Malta

Switzerland

Austria

Italy

USA

Australia

Tel.+49 2195 68994-0

Tel.+356 2220 7000

Tel.+41 32 675 35 51

Tel.+43 7676 20712 0

Tel.+39 349 259 4524

Tel.+1 401-294-6960

Tel.+61 3 98 01 19 06

info.de@seifertsystems.com info@seifertsystems.com info.ch@seifertsystems.com info.at@seifertsystem.com info@seifertsystems.com info.us@seifertsystems.com info@seifertsystems.com.au

Summary of Contents for 43152081

Page 1: ...ional principle 5 6 Technical data 6 7 Performance graph 7 8 Mounting 8 9 Mounting Principle 9 10 Cut out dimensions 10 11 Dimensions H x W x D 11 12 Electrical connection 12 13 Controller 13 14 Wiring diagram 14 15 Taking into operation 15 16 Trouble shooting 15 17 Maintenance Cleaning 15 18 Transport Storage 16 19 Parts supplied Spare parts Accessories 17 ...

Page 2: ...instruction manual must be adhered to General danger Indicates compulsory safety regulations which are not covered by a specific pictogram such as one of the following High electric voltage Indicates electric shock danger Important safety instruction Indicates instructions for safe maintenance and operation of the unit Attention Indicates possible burns from hot components Attention Indicates possi...

Page 3: ...d with regards to Safety instructions Instructions on taking the cabinet out of operation Instructions on the prevention of unauthorised cabinet reconnection The electric equipment meets the valid safety regulations One can find dangerous voltages above 50 V AC or above 100 V DC Behind the control cabinet doors On the power supply in the unit housing The unit has to be operated according to the typ...

Page 4: ...t air does not come into contact with the ambient air which may well be dirty or polluted Enclosure cooling units can dissipate large quantities of heat from sealed enclosures such as electrical enclosures into the ambient air and at the same time reduce the cabinet internal temperature to below that of the ambient air The unit can function without problems in extreme ambient conditions e g dusty ...

Page 5: ...he capillary pipe being a much lower pressure the refrigerant arrived to the evaporator where it absorbs the necessary heat to change from liquid to gas state The gas is then drawn back into the compressor completing the cycle Condensation management In environments with humidity and low internal enclosure temperatures condensation may form on the evaporator coil Standard cooling units 43XXX0XXX h...

Page 6: ...mpeded Ambient air circuit 280 500 cfm Cabinet air circuit 225 324 cfm Mounting Recessed Housing Material Mild steel powder coated Dimension H x W x D 41 x 17 8 x 10 6 inch Weight 105 lbs Cut out dimensions 15 5 x 36 8 inch Voltage Frequency 400 460 V 50 60 Hz 2 UL Voltage Frequency 400 460 V 60 Hz 2 Current 95F95F 2 9 A 50 Hz 2 5 A 60 Hz Starting current 5 3 A Max current 3 5 A Nominal power 95F9...

Page 7: ...Version Nr 1 8 21 06 2022 Doc No 9943152081 7 17 7 Performance graph ...

Page 8: ...he case a barrier or duct shall be provided to redirect the airflow Cooling unit enclosure air suction hole must be installed in the highest possible point When installing the unit on a door ensure it can take the weight Before drilling the enclosure ensure the fixing elements and couplings will not interfere with the equipment inside the enclosure itself Disconnect power before starting any work in...

Page 9: ...No 9943152081 9 17 9 Mounting Principle Do not use within the first 15 minutes after installation 1 M6 screws 2 M6 flat washers 3 M6 toothed washers 4 Cabinet 5 Sealing tape 6 Cooling unit 7 Lifting hook Fig 1 Recessed Fig 2 External ...

Page 10: ...Version Nr 1 8 21 06 2022 Doc No 9943152081 10 17 10 Cut out dimensions ...

Page 11: ...Version Nr 1 8 21 06 2022 Doc No 9943152081 11 17 11 Dimensions H x W x D ...

Page 12: ...ng to EN60730 1 8 4 A N O 6 4 A N C 2 2 A N O N C 250Vac 100000 cycles UL 873 8A resistive 2FLA 12LRA pilot duty C300 250Vac 30000 cycles These contacts are not suitable for fluorescent loads neon lights etc that use starters ballasts with phase shifting capacitors Fluorescent lamps with electronic controllers or without phase shifting capacitors can be used depending on the operating limits specifi...

Page 13: ...Press Set to save the new setting To change the heating set point St2 units with internal heater only 1 Press Set till St1 appears on the display and release the button 2 Press again Set till St2 appears on the display 3 Press the Up Down buttons to adjust the temperature 4 Press set to save the new setting Important Note when changing settings ensure that St2 5K St1 The unit also has a potential ...

Page 14: ... wire not present on KG4304 unit 2 Models with condensate evaporator C Controller EB External Blower IB Internal Blowers PC 9 Pole connector CC 7 core cable Mc Motor compressor AT Auotransformer 1 460V L1 2 400V L1 3 N L2 4 Earth 5 6 Alarm P1 7 Alarm P2 8 Door T1 9 Door T2 ...

Page 15: ...don t work Display shows alternating OFF and temperature The sequence of the phases inside the power supply connector is incorrect Change phases inside power supply connector Unit doesn t cool External and internal fan work compressor does not work Compressor motor electrical failure Have compressor replaced by qualified service technician Capacitor for compressor failed Replace capacitor Compresso...

Page 16: ...in the worst case could mean that the unit will not function The unit can only be stored in locations which meet the following conditions temperature range 40 F to 158 F Relative humidity at 77 F max 95 Returning the unit To avoid transport damage the unit should be returned in the original packing or in a packing case and must be strapped to a pallet If the unit cannot be returned in the original...

Page 17: ...Ltd Seifert Systems AG Seifert Systems GmbH Seifert Systems Ltd Seifert Systems Inc Seifert Systems Pty Ltd Albert Einstein Str 3 HF09 10 Wilerstrasse 16 Bärnthal 1 Rep Office 75 Circuit Drive 105 Lewis Road Hal Far Industrial Estate North Kingstown Wantirna South 42477 Radevormwald Birzebbuga BBG 3000 4563 Gerlafingen 4901 Ottnang 26100 Cremona RI 02852 3152 Victoria Germany Malta Switzerland Austri...

Reviews: