background image

Version No. 1-4 - 31.07.2022

Doc. No. 9943253001

9 / 18

8. Mounting

The power supply rating on unit rating plate must comply with mains rating.

 

 

Always disconnect the power supply before opening the unit.

The heat load to be dissipated from enclosure should not exceed specific cooling output of the unit at any
condition. At cooling unit selection always cater for a safety margin of at least 15% extra cooling output in the
worst conditions. 

Ensure that flows of air leaving and entering the cooling unit, internal and external, are not obstructed. It must
also be ensured in accordance with UL, that the air outlet is not blowing air directly at an equipment
operator. Should this be the case a barrier or duct shall be provided to redirect the airflow.

Cooling unit enclosure air suction hole must be installed in the highest possible point. When installing the unit
on a door ensure it can take the weight.

Before drilling the enclosure ensure the fixing elements and couplings will not interfere with the equipment
inside the enclosure itself. Disconnect power before starting any work inside the enclosure. Following this 1:1
Scale Drilling Template drill the holes and make the required cuts on the enclosure. This template may have
been affected by storage conditions, please check this template by verifying values of the largest dimensions
before drilling. Fit the sealing strip on the cooling unit on the side connected to the enclosure and follow the
installation diagram.

Note: In case of 19" rack mounted units please ignore the above mounting instructions.

Summary of Contents for 43253001

Page 1: ...onal principle 6 6 Technical data 7 7 Performance graph 8 8 Mounting 9 9 Mounting Principle 10 10 Cut Out Dimension 11 11 Dimension H x W x D 12 12 Electrical Connection 13 13 Controller 14 14 Wiring...

Page 2: ...issipation of heat from control cabinets and enclosures stationary not moving in order to protect temperature sensitive components in an industrial environment To meet the conditions of use all the in...

Page 3: ...nits based on the information diagrams or descriptions contained in this manual No liability can be accepted for damage and production caused by Disregarding the instruction manual Operating error Ina...

Page 4: ...regulations One can nd dangerous voltages above 50 V AC or above 100 V DC Behind the control cabinet doors On the power supply in the unit housing The unit has to be operated according to the type pl...

Page 5: ...air does not come into contact with the ambient air which may well be dirty or polluted Enclosure cooling units can dissipate large quantities of heat from sealed enclosures such as electrical enclos...

Page 6: ...apillary pipe being a much lower pressure the refrigerant arrived to the evaporator where it absorbs the necessary heat to change from liquid to gas state The gas is then drawn back into the compresso...

Page 7: ...750 1200 m h Cabinet air circuit 550 1200 m h Mounting Wall mounted Recessed Housing Material Mild steel powder coated Dimensions A x B x C D E 1 230 x 500 x 340 mm Weight 73 kg Cut out dimensions 1...

Page 8: ...Version No 1 4 31 07 2022 Doc No 9943253001 8 18 7 Performance graph...

Page 9: ...e case a barrier or duct shall be provided to redirect the air ow Cooling unit enclosure air suction hole must be installed in the highest possible point When installing the unit on a door ensure it c...

Page 10: ...No 9943253001 10 18 9 Mounting Principle Do not use within the rst 15 minutes after installation 1 M6 screws 2 M6 at washers 3 M6 toothed washers 4 Cabinet 5 Sealing tape 6 Cooling unit 7 Lifting hook...

Page 11: ...Version No 1 4 31 07 2022 Doc No 9943253001 11 18 10 Cut Out Dimension...

Page 12: ...Version No 1 4 31 07 2022 Doc No 9943253001 12 18 11 Dimension H x W x D...

Page 13: ...terminals are bridged on the female connector To connect the door contact switch remove the bridge and connect door contact switch The contact must be closed when the cabinet door is closed SCCR Refe...

Page 14: ...ress Set to save the new setting To change the heating set point St2 units with internal heater only 1 Press Set till St1 appears on the display and release the button 2 Press again Set till St2 appea...

Page 15: ...ontroller EB External Blower CE Condensate evaporator 1 Models with condensate evaporator IB Internal Blowers PC 9 Pole connector CC 7 core cable Mc Motor compressor AT Auotransformer 1 400V L1 2 460V...

Page 16: ...power supply connector is incorrect Change phases inside power supply connector Unit doesn t cool External and internal fan work compressor does not work Compressor motor electrical failure Have comp...

Page 17: ...ions which meet the following conditions temperature range 40 C to 70 C Relative humidity at 25 C max 95 Returning the unit To avoid transport damage the unit should be returned in the original packin...

Page 18: ...Seifert Systems AG Seifert Systems GmbH Seifert Systems Ltd Seifert Systems Inc Seifert Systems Pty Ltd Albert Einstein Str 3 HF09 10 Wilerstrasse 16 B rnthal 1 Rep O ce 75 Circuit Drive 105 Lewis Ro...

Reviews: